What happens when an EcoVAR loses a phase?

We are often asked what an EcoVAR does when it loses one or more phases of supply, and whether it can keep a de-energised line alive. It cannot.

The EcoVAR has no battery. It is three single-phase STATCOMs, one per phase, sharing a DC bus. That bus is a capacitor bank charged from the grid. It lets the EcoVAR move power between phases and supply reactive power, but it is not an energy source.

If any phase is lost, the EcoVAR stops compensating on all three phases and opens its grid relays. While the other phases stay energised, the controller remains on, so the event is logged and the unit can still be reached remotely. If all phases are lost, the unit powers down. Once supply returns and has been stable for the set reconnection delay, the unit reconnects automatically.

Short sags from motor and heat pump starts are handled differently. The EcoVAR injects maximum capacitive reactive power within 10 ms of phase voltage falling below 180 V, and holds this for up to 4 seconds by default. If the sag lasts longer, the unit trips and disconnects as it would for a lost phase. Protection settings follow AS/NZS 4777.2:2020 by default and can be changed for other standards. The rest of this bulletin sets out the detail.

The EcoVAR converts 230 V phase-to-neutral AC to about 800 V DC on a capacitor bus shared by the three phase converters. The shared bus is what allows active phase balancing: power drawn from a lightly loaded phase is delivered to a heavily loaded one. Net active power exchange with the network is limited to conversion losses. The capacitors hold enough energy to control current, not to supply load.

The EcoVAR is sometimes confused with the EcoSTORE, which adds battery storage to the same inverter platform. A standalone EcoVAR has no battery connected.

StateGrid relaysControllerCompensatingTypical trigger
RunningClosedOnYesNormal operation: voltage regulation, phase balancing, harmonic filtering
StandbyClosedOnNo (IGBTs off)Ready to operate, or compensation disabled
WaitingOpenOn while any phase is energisedNoAfter a trip or grid disturbance, until reconnection conditions are met
Powered downIsolated by breaker or fuseOffNoManual isolation, or loss of all phases

Whenever the controller is powered, the unit logs data and can be configured and interrogated remotely through EcoFLEET, which displays these state names.

A fast-acting control loop (10 ms time constant) overrides the slower Volt-VAR droop control (5 s time constant). When phase voltage falls below the sag threshold, that phase injects maximum capacitive reactive power to reduce the depth of the dip. This covers common sags from motor starts, heat pumps and air-conditioner compressors.

ParameterDefaultRange
Voltage sag/swell mitigationDisabledOn / Off
Sag threshold180 V150–230 V
Undervoltage delay (maximum capacitive injection)2 s0–4 s
Swell threshold265 V230–265 V
Overvoltage delay (maximum inductive absorption)1 s0–2 s

If the sag clears within the delay, the unit carries on. If it persists, the unit trips and moves to Waiting.

A lost phase is detected as a sustained undervoltage on that phase:

  • Below 70 V: immediate trip and disconnection.
  • Held between 70 V and 180 V, for example by downstream load or PV on an open conductor: trip after the undervoltage delay.
  • Unintentional island: the frequency-shift active anti-islanding function disconnects the unit within 2 seconds.

In Waiting, the relays are open and the unit does not inject onto any phase. The controller stays powered from the healthy phases, so the event is recorded and can be reviewed remotely.

With no supply, the controller loses power and the unit shuts down. The EcoVAR has no stored energy source and cannot energise the network.

Protective functionLimitTrip delayMaximum disconnection time
Undervoltage 2 (V<<)70 V1 s2 s
Undervoltage 1 (V<)180 V10 s11 s
Overvoltage 1 (V>)265 V1 s2 s
Overvoltage 2 (V>>)275 V–0.2 s
Under frequency (F<)47 Hz1 s2 s
Over frequency (F>)52 Hz–0.2 s

If a voltage excursion clears before the trip time, the unit returns to its previous operating point within 400 ms of voltage recovering.

After a trip, the unit reconnects automatically once voltage and frequency have stayed within limits for the grid connection delay. Range: 5–360 s.

The EcoVAR is not a generation source and cannot backfeed an isolated line. Inside the enclosure, the DC link capacitors can potentially hold lethal voltage for up to 10 minutes after power-down. Treat the unit as live until it has been metered.


EcoJoule Energy designs and manufactures low-voltage grid-edge power electronics in Brisbane, Australia. Its EcoVAR LV D-STATCOM is in field service with distribution utilities in Australia and internationally, and is available in pole-mount (EcoVAR Alto) and ground-mount (EcoVAR Terra) variants. EcoJoule’s technology relieves grid congestion and increases network hosting capacity, allowing the benefits of the energy transition to reach more users of the existing distribution network.

Dynamic phase balancing: fixing LV imbalance at the speed the load changes

Why service reallocation and augmentation no longer hold balance on feeders with single-phase EV charging, heat pumps and rooftop PV — and what a three-converter D-STATCOM does differently.

Phase imbalance on low voltage networks is not new. What has changed is the size and behaviour of the loads creating it, and the rate at which a balanced feeder becomes an unbalanced one.

Australian LV distribution is a four-wire multiple earthed neutral system, and almost every domestic connection is single phase. Historically that was manageable: individual loads were small, diversity across dozens of customers smoothed the per-phase totals, and a planner could allocate services across phases at connection and expect that allocation to hold for a decade.

Single-phase 7.2 kW EV chargers, heat pumps, electric hot water, reverse-cycle air conditioning and residential batteries break that assumption. One EV charger can represent more after-diversity demand than the five houses around it. Loads arrive where customers buy them, not where the network has headroom, and they cluster. One street adopts, the next does not. A feeder that measured within a few percent of balance at commissioning can sit 30 to 40 percent out on a winter evening, where the cold climate means that load diversity is simply all feeder heat pumps operating. Conversely, the imbalance moves during the day, as charging, hot water and cooling cycles overlap.

Unbalanced phase currents return through the neutral. In an MEN system the neutral is not a zero-volt reference; it carries current and develops a voltage along its length. That neutral shift moves the star point relative to the customer connections, so the heavily loaded phase drops further than its own load would explain, and the lightly loaded phases rise. The customer on phase C experiences a voltage complaint caused by loads on phase A.

The loss penalty follows the same currents.

ConditionPhase currentsNeutral currentConductor loss term
Unbalanced100 A / 60 A / 40 A53 A18,000 A²
Balanced66.7 A each0 A13,333 A²

Same total current delivered, unity power factor, equal phase and neutral conductor resistance. Balancing removes the neutral current and reduces conductor loss by approximately 26 percent.

WORKED EXAMPLE

Ia = 100 A at 0°    Ib = 60 A at −120°    Ic = 40 A at +120°

Real      = 100 − 30 − 20 = 50.0 A

Imaginary = −51.96 + 34.64 = −17.32 A

|In| = √(50.0² + 17.32²) = 52.9 A
Unbalanced: 100² + 60² + 40² + 52.9² = 18,000 A²

Balanced:   3 × 66.7² + 0²            = 13,333 A²

Reduction:  1 − 13,333 / 18,000 = 25.9%
Positive sequence         66.7 A  →  13,333 A²

Negative sequence         17.6 A  →     933 A²

Zero sequence (phases)    17.6 A  →     933 A²

Zero sequence (neutral)   52.9 A  →   2,800 A²

The distribution transformer is derated by the same mechanism: it reaches its thermal limit on the worst phase, not on its nameplate kVA. Imbalance therefore consumes three things a planner needs — voltage headroom, thermal capacity and network losses. It also consumes hosting capacity, because the same neutral shift that pulls one phase low pushes another high, and rooftop PV on that phase curtails first.

Service reallocation. A crew measures the pillar or the transformer over a week, identifies the loaded phase, and moves services across. It works, and it is inexpensive. It also requires a truck, a customer outage and a decision based on a snapshot. The measurement describes last month’s load pattern. The next EV connection, the next hot-water changeover or a shift in occupancy reverses it. Networks that rebalance on complaint are rebalancing the same feeders repeatedly.

Augmentation. A second transformer, reconductoring, or splitting the LV area fixes the peak with certainty. It also costs capital, takes months of design, easement and outage planning, and is sized for a load forecast that single-phase electrification keeps revising upward.

Conventional three-phase STATCOMs. A standard three-leg converter injects a balanced positive-sequence current. It can raise or lower all three phase voltages together, and it can correct power factor, but it cannot differentiate between phases. Applied to an unbalanced feeder it lifts the low phase and the already-high phases with it.

The EcoVAR is built as three independent single-phase STATCOM systems sharing a common DC bus. That architecture is the reason it can do something a conventional STATCOM cannot.

Because each phase has its own converter, the units can operate in opposite directions at the same instant. The converter on the heavily loaded phase supplies active power to the network; the converters on the lightly loaded phases absorb it. The shared DC bus is the transfer path. Net real power exchange with the network is close to zero, but the currents drawn from the transformer and the upstream conductor are balanced.

Active power balancing control manages this continuously. There are no discrete steps to select and no transformer taps to move. The device sets per-phase active and reactive current targets from the instantaneous measured condition and holds balance as the load profile changes through the day.

The control operates on instantaneous per-phase quantities rather than RMS values averaged over seconds, so correction occurs within a cycle.

This matters most for motor starting. A heat pump or air conditioning compressor draws several times its running current for a few cycles at start. On a weak single-phase connection that inrush produces a visible voltage dip, and through the neutral shift it disturbs the other two phases as well — the sag propagates to customers who did not cause it. A balancer that responds over seconds sees the event only after it has finished.

The EcoVAR supports the starting phase from the DC bus as the current rises, so the dip is contained at its source and does not couple across. The same mechanism handles PV inverter ramps, battery mode changes and EV charger step loads.

  • Balanced phase currents at the distribution transformer, held continuously rather than set once.
  • Neutral current and neutral voltage rise reduced, with the associated loss reduction.
  • Voltage spread between phases narrowed, recovering headroom for both load and PV export.
  • Sub-cycle containment of motor starts and step loads.
  • Installation on an energised network with no customer outage.
  • Per-phase measurement of the LV condition, available remotely, including after the correction is in service.

Phase imbalance created by single-phase electrification is dynamic. It changes hour to hour and grows year on year. Correction that is set manually, or that responds in seconds, is answering a question the network stopped asking. Dynamic balancing addresses it at the timescale it occurs, on the existing poles and wires.


EcoJoule Energy designs and manufactures low-voltage grid-edge power electronics in Brisbane, Australia. Its EcoVAR LV D-STATCOM is in field service with distribution utilities in Australia and internationally, and is available in pole-mount (EcoVAR Alto) and ground-mount (EcoVAR Terra) variants. EcoJoule’s technology relieves grid congestion and increases network hosting capacity, allowing the benefits of the energy transition to reach more users of the existing distribution network.

Network Planners’ Guide – The Smarter, More Economic Alternative to Network Augmentation

EcoJoule Energy’s Network Planners’ Guide explains how D-STATCOM technology provides network planners and engineers with a faster, more flexible and lower-cost alternative to conventional network augmentation, while improving voltage regulation, phase balance and power quality across increasingly complex distribution networks. Download the full guide here.

Executive Summary

Low-voltage electricity networks are under growing pressure from rooftop solar, electric vehicles, electrification and other distributed energy resources (DER), while much of the infrastructure supporting them was designed for a very different energy system.

The resulting overvoltage, undervoltage, phase imbalance, and power quality issues do not always indicate that a network has run out of capacity. Where the constraint is voltage or imbalance rather than thermal capacity, LV D-STATCOM technology such as EcoJoule Energy’s EcoVAR™ can provide a faster, more flexible alternative to traditional augmentation.

EcoVAR can be installed in approximately two hours with no customer outage, avoiding much of the engineering, construction and disruption associated with traditional network upgrades. In the illustrative example examined in this paper, the D-STATCOM solution delivers an annualised cost that is approximately 2.98 times lower than that of traditional augmentation. It can also defer major capital works and be redeployed as network requirements change.

The opportunity is not to replace augmentation where additional thermal capacity is genuinely required. It helps match investment to actual constraints, solve problems sooner, deploy capital more efficiently, and get more from existing network infrastructure.

D-STATCOM or Traditional Augmentation?

Traditional augmentation means reconducting LV lines, installing new transformers, or extending the medium-voltage supply to split feeders and shorten LV runs. Manual phase balancing, moving single-phase customer connections between phases, is also a form of augmentation.

A D-STATCOM is a form of augmentation. It requires no new HV line, no outage, and installation is under two hours. The engineering design is standard for all installations on a given network.

The limitation is explicit: a D-STATCOM does not add thermal capacity. Only augmentation does that.

Most voltage, imbalance and harmonic problems can be resolved without adding capacity. That is the selection test.

Three differences matter to a planner.

1. Speed – Connected in parallel to the existing network. No new spans, no new transformer, no new customer connections. Installed and commissioned in two hours. Augmentation projects run in days or weeks and include a customer outage.

2. Project Cost – The unit cost is comparable to that of a single transformer. The difference is the project around it: engineering design, outage management, traffic management, and construction lead time.

3. Redeployment – When capacity becomes the binding limit, an installed D-STATCOM can be moved. It is not customised to a site. Removal takes 15 minutes, and reinstallation takes two hours. Augmentation is fixed to the site where it is built.

Where a D-STATCOM Applies

A D-STATCOM, such as EcoJoule Energy’s EcoVAR, connects in parallel with the existing LV network and directly addresses voltage imbalance and harmonic problems. The technology is particularly applicable where the network is experiencing:

  • Overvoltage – Often associated with high levels of rooftop PV exporting onto an LV feeder.
  • Phase imbalance – Created when load and generation are unevenly distributed across the three phases.
  • Harmonics – Increasingly relevant as inverter-based and power-electronic devices proliferate.
  • Undervoltage on one or two phases – Where available capacity exists elsewhere across the three-phase network.
  • Voltage sags, swells and flicker – Where dynamic voltage support can improve local power quality. 

Selection Guide

Observed problemOutcomeReason
OvervoltageCost a D-STATCOM projectActive power is not the limit, so the device always has authority.
Phase imbalanceCost a D-STATCOM projectAt least one phase carries excess active power. Active phase transfer corrects it.
HarmonicsCost a D-STATCOM projectHarmonic correction is not limited by active power.
Undervoltage on one or two phasesCost a D-STATCOM projectA single-phase power limit. Correctable by transfer between phases.
Undervoltage on all three phasesTraditional augmentation projectA thermal capacity limit. A D-STATCOM does not add capacity.
LV network at end of lifeBoth, in sequenceInstall the D-STATCOM to hold power quality while the augmentation is designed, then redeploy it.

Calculating the Benefits

The real cost of solving an LV network constraint extends well beyond the upfront price of the equipment.

Traditional augmentation may deliver infrastructure with an asset life measured in decades, while a D-STATCOM has a shorter life but offers something conventional infrastructure cannot: the flexibility to be removed and redeployed as network needs change.

A simple capital-cost comparison therefore does not compare like with like. A more meaningful approach is to compare the cost of delivering the required network outcome over time.

Equivalent Annual Cost (EAC) provides that comparison by annualising each component according to its cost, expected asset life and discount rate:

EAC = C ÷ [(1 − (1 + r)^-n) ÷ r]

Each project component retains its own asset life, allowing long-life infrastructure, engineering, installation and equipment costs to be assessed consistently. This provides planners with a clearer picture of the long-term economics of each approach rather than focusing solely on initial capital expenditure.

The Value of Deferring Augmentation

The decision is not always D-STATCOM or traditional augmentation. Where additional thermal capacity will eventually be required, a D-STATCOM can address the immediate voltage or phase constraint while allowing major augmentation to occur when that additional capacity is actually needed.

Deferral can postpone significant capital expenditure, potentially move investment into a future regulatory period and provide more time to understand how DER penetration and demand will develop.

Importantly, the investment does not have to become stranded when augmentation eventually occurs. If the D-STATCOM still has useful service life, it can be redeployed to another constrained feeder, extending the value of the original investment.

The objective is not to avoid necessary augmentation. It is to solve today’s constraint efficiently, preserve future options and invest in permanent network capacity when the network actually needs it.

How a D-STATCOM Works

The D-STATCOM is a three-phase power electronic device connected to the LV network in parallel. It is three independently controlled inverter-STATCOMs, one per phase, with a common shared 864V nominal DC bus.

Two control actions run at the same time.

  • Reactive Injection – The unit exchanges reactive current with the network at the point of connection. The voltage change is approximately: ΔV ≈ Q·X / V, where Q is the injected reactive power, X is the upstream reactance and V is the nominal voltage. The unit works against upstream impedance. More upstream reactance gives more voltage authority.
  • Active Phase Transfer – The unit moves real power between phases through a shared DC bus. This corrects imbalance directly rather than compensating negative sequence current alone. Active harmonic filtering runs on the same hardware, injecting harmonic current in antiphase.
Expected Voltage Correction

Worked case: 95 mm² aluminium overhead conductor, R ≈ 0.32 Ω/km, X ≈ 0.29 Ω/km, X/R ≈ 1, 1 MVA distribution transformer, 40 kVAr device.

Distance from transformerVoltage correctionAs percentage
500 m≈ 16 V4.00%
750 m≈ 22.5 V5.60%

Transformer rating has little effect at the feeder end. At 750 m, line reactance is about 95% of total upstream reactance, so a 500 kVA and a 1 MVA transformer give nearly the same result.

Two limits apply. Reactive injection does not correct voltage drop caused by real load current through line resistance. On an underground cable, X/R is lower and correction per kVAr is lower than the figures above.

D-STATCOMs still work in both cases, but the total voltage change per unit may be lower. Multiple STATCOMs can be connected to the same LV network to increase power if necessary. It is rare, even on aerial bundled conductor (ABC) networks, to need more than one 40 kVAr unit per LV feeder.

Site Selection

Place the unit near the voltage or imbalance problem. Most installations fall between 50% and 80% of the way along the LV feeder, but that range is a guide rather than a rule. Position follows the problem.

Move toward 50% where PV generation is concentrated in the middle of the feeder, or where the LV line can be backfed. Move toward the far end where the deviation is worst at the end. A shift of a few spans either direction makes no material difference to the result.

Within that zone, select the cheapest site to build. Where the electrically preferred pole carries streetlighting, fuses or telecommunications equipment, or where vegetation restricts access, move to the next clean pole. Installation cost dominates the difference; electrical position does not.

Where smart meter data is available, use it to identify the spans and phases with the most frequent and most severe deviations. This reduces selection to a short list of candidate poles.

Voltage is held closest to setpoint at the point of connection, but the effect is seen along the whole feeder.

A head-end tap changer translates the entire profile: it can be set for midday or for evening, not both. A D-STATCOM at the constrained node holds that node at setpoint and reverses between absorbing and injecting as conditions change.

Connecting a D-STATCOM to the Network

The unit connects in shunt. The feeder continues to carry its load and does not need to be de-energised to connect or remove the unit. There is no customer outage.

Every shunt connection needs overcurrent protection and a means of isolation. Three arrangements are used. All three perform identically. The choice is a work practices decision, not a technical one.

ArrangementIsolation methodWhen it is used
Outdoor fusesPull the fusesLowest cost, fewest components. Not available where technicians may not pull live LV fuses.
Switchboard with circuit breakerOpen the breakerWhere live fuse pulling is prohibited by work practices.
Switchboard with breaker, backup fuses and SPDOpen the breakerWhere surge protection is required by network standard.

Rating is 100 A, whether fuse or breaker. Rated current is 63.5 A continuous, with short-time capability of 1.5 × rated, approximately 95 A. Most off-the-shelf MCBs derate at elevated ambient temperature. At the unit’s 50°C maximum, a marginally sized breaker can trip at full output. A 100 A device holds margin above the derated threshold while remaining low enough to protect the connection. Confirm that the shunt connection conductors are rated to carry 100 A.

Notes for Protection Engineers

  • The D-STATCOM is not an energy storage device. It sources power from the line side. Loss of phase or loss of supply removes it from the circuit.
  • Onboard capacitors discharge over approximately one minute on loss of mains.
  • The protective device on the overhead connection is 100 A, fuse or MCB, subject to work practices.
  • Anti-islanding is handled by internal relays. Undervoltage and underfrequency disconnect settings are configurable and are shipped to IEC 62477 inverter settings.
  • As a utility-grade device, the disconnect range is often widened on commissioning. This allows the unit to correct voltage during a sag rather than disconnecting, and to connect to a non-compliant voltage and then bring it into compliance.
  • The tests highlighted in this white paper are intended to be run by the planner on network data and cost data that the planner controls.
  • A D-STATCOM will not suit every site. Where the constraint is thermal, it does not apply. Where it does apply, the annualised cost comparison should be run and recorded either way.

For More Information

Martin van der Linde
Chief Commercial Officer
EcoJoule Energy Pty Ltd
sales@ecojoule.com

Volt-VAR Droop and Active Power Balancing in the EcoVAR LV STATCOM

How the two simultaneous control loops in a three-phase LV STATCOM work, and what each one can and cannot correct.

1. Summary

  • The EcoVAR uses three independently controlled single-phase inverter stages connected to one shared DC bus.
  • A Volt-VAR droop curve sets reactive power as a function of measured voltage. The EcoVAR evaluates that curve against each phase voltage separately, so one phase can absorb VArs while another injects them.
  • A second loop, Active Power Balancing, runs at the same time. It moves real power from lightly loaded phases to heavily loaded phases through the shared DC bus.
  • The two loops correct different things. Reactive power shifts each voltage as well as the average voltage; active power transfer corrects the difference between phases and reduces neutral current. Neither substitutes for the other.
  • Both loops operate from voltage measurement only. No series current transformers are required, so installation does not depend on breaking the conductor.

2. What a Volt-VAR droop curve does

A Volt-VAR droop curve is a piecewise-linear rule that converts a measured voltage into a reactive power command. It is defined by four voltage set points and applied continuously, without operator intervention or a network communications link.

Below the lower set point the STATCOM sources reactive power (capacitive operation), which raises voltage at the point of connection. Above the upper set point it sinks reactive power (inductive operation), which lowers voltage. Between the two inner set points the output is zero. That deadband stops the unit from responding to normal small voltage variations.

The EcoVAR follows the generator sign convention: a positive reactive power reference is capacitive (sourcing VArs), a negative reference is inductive (sinking VArs). The characteristic is as described in AS/NZS 4777.2:2020 and similar international standards like EN50549, with leading and lagging slopes that can be set symmetrically or asymmetrically.

Figure 1 — Volt-VAR droop characteristic. Set points shown are an example only.

3. Configurable set points

All four set points are user-configurable from the EcoVIEW engineering tool or by uploading a settings file through EcoFLEET Manager. A limited set is also available over DNP3 and Modbus.

Set pointRangeFunction
V1180 – 225 VAt and below V1 the phase holds maximum capacitive output.
V2185 – 250 VLower edge of the deadband. Capacitive output falls linearly from V1 to zero at V2.
V3185 – 260 VUpper edge of the deadband. Inductive output starts here.
V4190 – 277 VAt and above V4 the phase holds maximum inductive output.

Rated output is 40 kVAr total, 13.33 kVAr per phase, available in both directions across 210 V to 277 V. The unit continues to operate down to 180 V at a maximum continuous 63.5 A per phase, and tolerates connection to any voltage from 0 V to 280 V without damage.

4. Three inverter stages, one DC bus

The EcoVAR is not a single three-phase bridge producing a balanced output. Each phase is served by an inverter stage with its own current control loop, and all three stages are connected to a common DC bus. Two consequences follow directly from that architecture.

First, each stage can be commanded independently. The droop curve is evaluated three times each control cycle, once per phase, against that phase’s own measured phase-to-neutral voltage. One phase reaching its current limit does not constrain the other two.

Second, active (real) power can be moved between phases. Because the three stages share a DC bus, power drawn from one phase can be injected into another without a battery and without any net exchange of energy with the network.

Figure 2 — Active power transfer between phases through the shared DC bus.

5.  A single characteristic, three independent evaluations

The three phases share one droop characteristic — the same four set points and the same slopes apply to all of them. What is independent is the input and the output, not the configuration. Each stage measures its own phase voltage and produces its own reactive power command from the shared curve.

This is what allows the EcoVAR to reduce voltage unbalance rather than simply shift the whole voltage profile. On a feeder where L1 sits at 252 V under high PV export and L3 sits at 228 V under load, the same curve puts L1 into full inductive operation and L3 into capacitive operation at the same instant.

The unit can alternatively be configured to act on the average of the three phase voltages. That mode is available for networks whose standards require it, but it gives a poorer voltage outcome for customers and is not the recommended setting.

6.  The second loop: Active Power Balancing

Reactive power alone corrects voltage well on reactive networks. On resistive LV networks — underground cable, long aluminium mains, heavily loaded urban feeders — voltage responds more strongly to real power than to reactive power, and reactive injection alone cannot bring the phases together.

Active Power Balancing addresses this. The EcoVAR takes the three phase voltages as a proxy for phase loading: a higher voltage implies a lighter load, a lower voltage implies a heavier one. It then transfers real power from the lighter phases to the heavier ones in proportion to the voltage differences, subject to the constraint that the three phase powers must sum to zero. This reduces current unbalance on the feeder and neutral current at the transformer.

Using voltage as the proxy avoids series current transformers. That removes both the cost and the outage that a CT installation would otherwise require.

Two modes are provided. Gain-based transfer injects real power per phase in proportion to the deviation from the average voltage, with a user-selected P or Q priority that determines which is curtailed first if a phase reaches its apparent power limit. Optimal X/R computes a reference apparent power per phase from a voltage droop and then splits it into active and reactive components according to the source impedance X/R ratio, which is taken from the network model or estimated at commissioning. Active Power Balancing is disabled by default and is enabled per site.

7.  Why both loops are needed

The two loops are subject to different constraints, and that is the whole reason for running them together.

 Volt-VAR droop (Q)Active power balancing (P)
Quantity controlledReactive power per phaseActive power transfer between phases
Network constraintLimited only by the per phase apparent power rating of the unitSum of the three phase powers must be zero
Effect on average voltageCan raise or lower all three phases togetherNone — the three voltage changes sum to zero
Effect on unbalanceReduces it, most effectively on reactive networksReduces it, most effectively on resistive networks
Effect on neutral currentIndirectDirect reduction at the transformer
Default stateEnabledDisabled — enabled per site

If all three phase voltages are high, transferring real power between them cannot bring any of them down, because whatever one phase gains another must lose. Only reactive power can move the average. Conversely, on a resistive feeder with one badly loaded phase, reactive power struggles to close the gap and real power transfer does it efficiently. Running both loops covers both cases across the full range of LV network impedances.

8.  Control loop timing

FunctionResponse
Internal current control loop10 – 90% rise and fall in 2 ms or less
Volt-VAR droop response (ramp-rate limited)Default 5 s, to keep the steady-state response smooth. However, can be set sub-cycle for fast response, typically when Active Power Balancing is disabled.
Voltage sag and swell limiting10 ms time constant; overrides the droop response
Reactive current overshootNo more than 5% of steady-state output

The current loop is fast enough to respond within a tenth of a cycle. The droop response is deliberately slowed to five seconds so that the unit regulates steady-state voltage rather than chasing transients. Fast events are handled separately: if a phase reaches 180 V or 277 V, the sag and swell function commands maximum reactive power with a 10 ms time constant and overrides the droop.

9.  What to specify at commissioning

  • Four droop set points, plus symmetrical or asymmetrical slopes.
  • Per-phase control enabled, or average-voltage mode if a network standard requires it.
  • Active Power Balancing: disabled, gain-based, or optimal X/R.
  • For gain-based operation: P priority or Q priority, chosen from the local X/R ratio — Q priority for overhead and other reactive feeders, P priority for cable and other resistive feeders.
  • For optimal X/R operation: the X/R ratio, from the network model or estimated during commissioning.

For settings files, network studies or a copy of the EcoVAR ALTO user manual, contact EcoJoule Energy at sales@ecojoule.com or your regional distributor.  

EcoJoule Adds Malaysia To Growing Global Footprint

Australian energy grid technology company EcoJoule Energy has secured its first sale into Malaysia, marking another significant milestone in the company’s international expansion and adding one of Southeast Asia’s most important electricity markets to its growing global footprint.

The sale to Tenaga Nasional Berhad (TNB), Malaysia’s national electricity company and operator of the electricity grid throughout Peninsular Malaysia and Kuala Lumpur, includes multiple EcoVAR™ ALTO pole-mounted STATCOMs and EcoSTORE™ pole-mounted Battery Energy Storage System (BESS) units.

The first shipment of EcoVAR units left Australia this week, with the EcoSTORE units to leave in approximately eight weeks.

The agreement further expands EcoJoule Energy’s international presence, which now spans almost ten countries, including Australia, New Zealand, Hong Kong, Belgium, Spain, the United Kingdom, Lithuania, Israel and now Malaysia.

EcoJoule Energy Founder and CEO Dr Mike Wishart said the new sale reflected growing global demand for technologies that help electricity networks manage the growth of renewable energy and the impact on the energy grid.

“Malaysia represents an important new market for EcoJoule and demonstrates the increasing international recognition of Australian innovation in electricity network management,” Dr Wishart said.

“Across the world, network operators are facing many of the same challenges. As solar penetration continues to increase, particularly on distribution networks, utilities need smarter and more flexible ways to manage voltage stability and power quality.”

“We are seeing strong demand for STATCOM technologies because they provide a highly effective solution for maintaining grid stability, while enabling greater levels of renewable energy integration.

“Utilities are looking for practical, cost-effective tools that help them manage the energy transition without relying solely on traditional network augmentation that can cost tens of millions of dollars.”

“The challenges facing electricity networks in Asia, Europe and Australia share a common theme – the transition to cleaner energy is creating increasingly dynamic and complex power flows. EcoJoule’s technologies are designed specifically to help networks adapt to that transition efficiently and sustainably.”

Solving Complex, Pressing Grid Issues

EcoJoule Chief Commercial Officer Martin van der Linde said the Malaysian deployment highlighted the versatility of the company’s technology platforms and its ability to address a broad range of network challenges.

“Our EcoVAR and EcoSTORE platforms have been developed to solve some of the most pressing issues facing modern electricity networks,” Mr van der Linde said.

“What makes the technology unique is its ability to address multiple challenges through a flexible, pole-mounted solution that can be rapidly deployed where it is needed most.”

“Whether utilities are dealing with voltage variability caused by rooftop solar, phase imbalance, peak demand constraints, increasing electrification, or the need for distributed energy storage, our technology provides network operators with greater visibility, control and flexibility.”

“The global energy transition is creating increasingly complex energy flows throughout distribution networks. EcoJoule’s solutions help operators manage that complexity while maximising the use of existing infrastructure and improving reliability for customers.”

EcoVAR™ is a pole-mounted Static Synchronous Compensator (STATCOM) that uses advanced power electronics and software to regulate voltage and reactive power on low-voltage networks in real time. The technology enables network operators to integrate greater levels of distributed renewable energy and electrification technologies while improving power quality and reducing the need for costly network upgrades.

EcoSTORE™ is EcoJoule’s pole-mounted battery energy storage platform, designed to provide distributed storage capacity within local electricity networks. The system helps manage peak demand, supports renewable energy integration, improves network resilience and enables more efficient utilisation of grid infrastructure.

The Malaysian project follows a series of successful deployments of EcoJoule technologies across Australia and international markets, reinforcing the adaptability of the company’s solutions across diverse network conditions and regulatory environments.

Established nearly a decade ago, EcoJoule Energy is a 100 per cent Australian-owned company providing innovative solutions that help electricity distributors integrate renewable energy, improve power quality and manage grid reliability.

Why D-STATCOMs deliver faster fixes for Low Voltage Network Power Quality

A D-STATCOM (Distribution LV STATCOM) and a feeder augmentation can both bring an LV feeder back inside voltage limits. They differ in how much engineering, land access and switching work sits between identifying the problem and the network being compliant. Four reasons the D-STATCOM path is shorter.

1. A D-STATCOM uses the existing poles and wires

An augmentation project changes the network’s physical assets. That means a feeder civil design: pole loading and strength assessment, conductor selection, clearance checks, possible easement or land acquisition for a new substation site, and design approval before any works order issues.

A D-STATCOM changes the network’s electrical behaviour without changing its topology. The EcoVAR Alto mounts on an existing pole; the EcoVAR Terra sits on a pad. Both connect to the existing LV mains. No conductor replacement, no new feeder route, no land acquisition. The civil design and land access critical path is removed, not shortened.

2. D-STATCOMs connect in parallel, not in series

A series device sits in the supply path. Installing it requires an LV outage, customer notification and a switching programme, and once installed it becomes a single point of failure between the transformer and the customer.

A D-STATCOM connects in parallel through its own protection. Consequences for delivery:

  • Installation is a live connection — no planned outage, no notification process, no switching programme.
  • An internal device fault operates the device’s protection and disconnects the unit. Supply to customers is unaffected; the network returns to its pre-installation condition.
  • No new customer-interruption failure mode is introduced into the supply path, so the reliability case is straightforward.

3. One construction design per LV line type, used network-wide

The D-STATCOM installation is feeder-agnostic. The arrangement depends on the line construction, not on the feeder’s loading, length or fault level.

In practice, standards teams develop one standard arrangement per LV construction type in their network — bare conductor, aerial bundled conductor, underground pad-mount — and then apply it everywhere. Design effort becomes a one-off standards exercise rather than a per-project one. Once the standard arrangement exists, each subsequent site is a works order, not a design job.

4. The settings are generally common to every site but can be easily modified if required

The EcoVAR combines two control systems in one unit:

  • Volt-VAR reactive control for voltage regulation and power factor.
  • Simultaneous active power balancing control (patented) that transfers real power between phases to correct imbalance and neutral current.

Both controls act in closed loop on conditions measured at the point of connection. They are generally not tuned to a modelled feeder, so the setting file does not change site to site. One approved setting file covers the network. On occasions, for unusual sites (eg. Excessively weak low voltage feeders) the settings can be easily remotely modified.

That has direct operational consequences: spares are interchangeable across the fleet, a hot swap needs no re-engineering, and a crew can redeploy a unit from one site to another without a new study.

The net effect

The first D-STATCOM deployment carries the standards work: one arrangement per line type, one approved setting file. Every deployment after that is procurement plus a works order. Augmentation repeats the design, approval and outage cycle at every site.

Next step: EcoJoule can provide sample GA drawings for EcoVAR D-STATCOM installations, together with standard configuration for the Volt-VAR Droop curve. Contact EcoJoule for more information.

Why engineers choose the EcoVAR D-STATCOM over network augmentation

Australia’s low-voltage networks are facing growing pressure from rooftop solar, EVs and changing patterns of electricity demand. For network engineers, managing the resulting voltage and power-quality issues has traditionally required costly and time-consuming network augmentation.

EcoJoule Energy’s EcoVAR D-STATCOM provides an alternative. Installed directly on the LV network, EcoVAR uses advanced power electronics to dynamically manage voltage, reactive power and phase imbalance without major infrastructure upgrades.

It does not replace augmentation where additional network capacity is required. Instead, EcoVAR gives engineers a faster, flexible and deployable option for addressing common LV constraints, improving network performance and potentially deferring capital expenditure.

Six problems now account for the majority of LV feeder complaints and constraint reports. The EcoVAR addresses all six from a single pole-mounted unit.

ProblemTypical cause on the LV feederEcoVAR response
OvervoltageReverse power flow from rooftop PV raising feeder voltage above the statutory limit, worst at the feeder extremities in the middle of the day.Absorbs reactive power and rebalances phase loading to reduce voltage at the point of connection.
UndervoltageCoincident evening demand from EV charging, heat pumps and air conditioning at the end of long feeders.Injects reactive power and transfers real load between phases to raise voltage.
Voltage unbalanceSingle-phase PV, EV chargers and heat pumps connected unevenly across the three phases.Actively transfers real power between phases, reducing unbalance, peak phase current, neutral current and feeder losses.
Voltage sagsStep changes in LV load such as motor starting, welding plant and DC fast charging.Sub-cycle detection and response limits the depth and duration of sags originating on the LV network. Sags originating from upstream HV faults are outside its scope.
HarmonicsRectifier front ends in PV inverters, EV chargers, variable speed drives and switched-mode power supplies.Active harmonic filtering injects counter-phase current on selected harmonic orders.
FlickerFluctuating load and rapidly varying generation on high-impedance and SWER-fed networks.Continuous dynamic response holds voltage through the fluctuation, reducing Pst and Plt.

Why the excursions matter

ConsequenceWhy it drives action
Regulatory compliance and licence riskSteady-state voltage limits are a statutory or licence obligation. Sustained excursions are reportable non-compliance, and the duty to correct sits with the distributor regardless of which connection caused it.
Customer complaints and cost to serveEach excursion generates complaints, site visits and repeat investigation on the same feeder until the cause is found. Complaint volume is itself a reported performance measure.
Equipment that will not operateVoltage outside the operating window causes EV chargers to derate or stop, PV inverters to trip and lose customer generation, and sensitive electronics to fail. As electrification scales, a charger that will not deliver is read by the customer as a network failure.

Why these problems are growing

The LV network was designed to deliver diversified, unidirectional power to loads of a few kilowatts each. Four changes have invalidated that design basis, and all four act on the same conductors:

ChangeEffect on the LV network
Gas heating to heat pumpsAdds several kilowatts of coincident winter evening load per premises.
EV chargingAdds 7 to 22 kW single-phase point loads with high coincidence after work hours.
Rooftop PVReverses power flow for part of the day and raises voltage at the feeder extremities.
High power electronicsInjects harmonic current and concentrates load unevenly across phases.

The network was never built for bidirectional flow at these power levels, and rebuilding it to suit is not economically feasible at the scale or pace the transition requires.

The traditional answer: augmentation

Augmentation resolves the constraint by reducing feeder impedance or adding capacity. It works, and it carries a fixed set of costs on every project:

Cost driverWhat it means in practice
Bespoke engineeringSite-specific design, load flow study and construction package for each location.
Approvals and accessEasements, consent, traffic management and environmental approvals.
Lead timeDesign to energisation typically measured in months, against constraints that are emerging in weeks.
Customer outagePlanned interruptions to complete the work, with the associated notification and reliability impact.
Stranding riskCapital committed to one location for the life of the asset, whether or not the constraint stays there.

What the EcoVAR does differently

The EcoVAR is a low voltage D-STATCOM. It differs from a conventional STATCOM in one respect that matters on LV feeders: it combines Volt-VAR reactive control with active phase balancing.

LV feeders are resistance-dominated. A conventional STATCOM controls voltage by exchanging reactive power, which acts on the reactive component of line impedance. On a feeder with a high R/X ratio that lever is limited, which is why reactive-only compensation is often ruled out for LV voltage correction.

The EcoVAR also transfers real power between phases through its 864 VDC secondary bus, acting on the resistive component. The two mechanisms together give the EcoVAR voltage authority on feeders where reactive compensation alone would not be sufficient, without reconductoring.

Installation and deployment

AttributeEcoVAR
Installation timeUnder two hours on a single existing pole.
Outage requiredNone. The unit is connected live to the LV network.
Engineering per siteNone. No bespoke design package, no reconductoring.
RedeploymentThe unit can be relocated when the constraint moves, so capital is not stranded.

The cost comparison

EcoJoule compares options on an equivalent annual cost (EAC) basis, which normalises assets with different capital costs and different lives. On that basis, modelling across a range of network cases shows the EcoVAR annualised cost is generally one third or less of the augmentation option that resolves the same constraint, driven by lower installed capital and the ability to redeploy the asset. The result is more constraint resolved per dollar of capital budget, and a lower cost outcome for the customers who pay for the network.

EAC outcomes depend on the augmentation scope being displaced, the discount rate and the asset lives assumed. EcoJoule can run the comparison against your own assumptions.

Where augmentation is still required

The EcoVAR does not add conductor or transformer rating. That matters less in practice than it first appears, because of how LV constraints actually present:

ConstraintRole of the EcoVAR
Genuine thermal limit on a balanced feederAugmentation is required. The EcoVAR restores voltage compliance within two hours while the augmentation project moves through the backlog, then redeploys to the next site once the works are energised.

Deferral economics

Because the unit is redeployable, it does not have to displace an augmentation project to earn its return. It only has to delay it. EcoJoule’s modelling indicates a deferral of approximately two years is sufficient for the EcoVAR to return its cost across most network cases. Where the augmentation backlog already exceeds twelve months, that threshold is largely met by the queue alone.

Where voltage non-compliance is already occurring and the augmentation project is a year or more from energisation, the alternative to the EcoVAR is not a faster upgrade. It is another year of non-compliance.

Request the comparison for your network

The EAC cost comparison model and supporting application notes are available on request.

sales@ecojoule.com

EcoVAR ALTO™ Commissioning Checklist Now Available

EcoJoule Energy has released a commissioning checklist for the EcoVAR ALTO™ 40 kVA LV STATCOM, available to customers and appointed installation contractors on request.

EcoJoule Energy has released a commissioning checklist for the EcoVAR ALTO™ 40 kVA LV STATCOM. It is available to EcoJoule customers and their appointed installation contractors on request.

A trained crew installs and commissions an EcoVAR ALTO™ in under two hours, with no LV outage. Most of that time is mechanical. The commissioning steps that follow give clarity for a successful installation.

EJ-FRM-OPS-CHECK-0071 covers seven stages, from receipt of the pallet to signed sign-off:

  • Pre-installation ground checks
  • Site and mechanical installation
  • Electrical connection
  • Inspection before commissioning
  • Startup and commissioning procedure
  • Operational verification
  • Commissioning sign-off

Every check is referenced to the section of the EcoVAR ALTO™ User Manual that explains it, so a crew resolves a question at the pole rather than calling the depot.

The sign-off page records serial number, pole or asset number, modem IP address, settings applied and first-run measurements.

Document details

Document IDEJ-FRM-OPS-CHECK-0071
TitleEcoVAR ALTO™ Commissioning Checklist
Version1 — initial release
Issued14 August 2026
Applies toEcoVAR ALTO™ 40 kVA LV STATCOM (Model EV40), pole-mounted on the LV overhead network
AvailabilityEcoJoule customers and their appointed installation contractors, on request

How to request a copy

Email service@ecojoule.com. If you have an installation programme starting, tell us the crew size and we will walk your commissioning engineers through the EcoFLEET™ steps beforehand.

About EcoJoule Energy

EcoJoule Energy designs and manufactures low voltage grid equipment in Loganholme, Queensland. The EcoVAR LV STATCOM regulates voltage, balances phases and filters harmonics on the distribution network.

Why add remote communications to your LV STATCOMs

What a connected EcoVAR gives a distribution utility, and how the connection is made.

Most utilities can describe the state of their HV and MV networks in near real time. Below the distribution transformer, the picture thins out. Smart meters report at the point of supply, usually on 15 or 30 minute intervals, and they tell you what a customer connection looked like, not what the feeder was doing between the readings.

An LV STATCOM sits in that gap. It is already measuring the LV feeder continuously, because it has to: voltage, current and harmonic content on each phase are the inputs to its control loop. Whether that measurement stays inside the unit or reaches your planning and operations teams is a decision made at installation, and it costs very little to make the right one.

This article sets out three reasons to connect your LV STATCOMs, and then the practical detail of how it is done on the EcoVAR.

1. Visibility of the LV network

A connected EcoVAR reports three classes of data that most utilities have never held for the LV network at scale.

Voltage. Per phase voltage, as well as STATCOM current, active and reactive power, at the point of installation, at a resolution well beyond metering intervals. Because the EcoVAR is typically installed at the electrical problem, at the end of a long feeder or on a section with heavy solar export, the data comes from the location where your planning assumptions are least reliable. Phase by phase reporting also quantifies imbalance directly, rather than inferring it from connection records that may be decades out of date.

Harmonics. Individual harmonic orders and total distortion, per phase, over time. Harmonic distortion on LV networks is rising with inverter based generation, EV charging and switched mode loads, and most utilities have no ongoing measurement of it. Connected EcoVARs give you a distortion baseline for the sections where you have units installed, and a time series that shows when distortion is worst and how it correlates with load and generation.

Oscillography. Triggered waveform captures around events: voltage dips, transients, and protection operations. This is the class of data that separates a monitoring device from a meter. When a customer reports flicker or equipment damage, a waveform capture from the LV feeder gives an engineer something to analyse rather than something to guess at.

None of this displaces smart metering. It complements it. Smart meters tell you about load profile and customer experience at the connection point. A connected STATCOM tells you about the behaviour of the feeder itself, including reactive power flow and distortion that metering does not report.

The data is available for export into network modelling, digital twin and visualisation platforms. Measured LV voltage and harmonic profiles improve the calibration of LV models that are otherwise built on assumed diversity factors and nominal impedances. For utilities running LV network visibility programmes, connected STATCOMs are an additional measurement layer at sites you were already investing in.

2. Remote adjustment of setpoints and droop curves

An EcoVAR is commissioned with a voltage setpoint and a droop characteristic that suit the feeder as it is understood on the day. Feeders change. Solar penetration increases, EV charging arrives, load transfers occur, and seasonal load composition shifts.

With communications in place, setpoints and droop curves are changed from the office. Without them, every settings change is a truck.

Conservation Voltage Reduction

Conservation Voltage Reduction (CVR) is the deliberate operation of the distribution network toward the lower end of the permitted voltage range in order to reduce energy consumption and peak demand. It works because a meaningful share of connected load is voltage dependent. Resistive heating, some lighting, motors and transformer no load losses all draw less power at lower voltage, and lower voltage also reduces network losses.

The metric used to quantify the effect is the CVR factor: the percentage reduction in demand or energy per one percent reduction in voltage. Published studies commonly report values of about 0.5 to 1.0 for active energy, with higher factors for reactive power and seasonal variation depending on load composition. Utility programmes typically report energy savings in the range of 1 to 4 per cent, achieved without any action by customers.

The constraint on CVR is the low point. A utility can only lower voltage until the worst served customer on the worst feeder reaches the statutory minimum. Everything above that point is headroom the utility cannot use.

This is where LV reactive support and CVR intersect. An EcoVAR clamps the voltage at the new setpoint on the network, controlling the voltage down the LV feeder, not simply at the transformer.

Communications make that relationship manageable. As a CVR programme is tuned, the target voltages at the LV support points need to move with it, seasonally and as the network changes. Doing that remotely across a fleet is straightforward. Doing it with field visits is not.

3. Condition monitoring and evidence led maintenance

The EcoVAR requires no scheduled maintenance. There are no filters to change, no fans to service and no consumables. Stated plainly, that means a time based maintenance programme adds cost without adding reliability.

The alternative is to attend site when the equipment tells you to. A connected fleet reports internal temperatures, converter status, alarm and event history, availability, and the reactive power the unit is actually delivering against what the network is asking of it. That supports three decisions a maintenance planner needs to make:

  • Which units, if any, need attention.
  • Whether a reported network problem is the STATCOM or the network.
  • Whether units are correctly sized and set for the feeders they are on, or whether some are running at their limits while others are barely working.

The third point tends to be the one that changes budgets. Fleet data shows where a unit is under utilised and could be redeployed, and where a feeder has outgrown the support installed on it.

There is a fair objection here. If the equipment is maintenance free, why monitor it? Because maintenance free is a statement about scheduled intervention, not a claim that nothing will ever need attention. Monitoring is what lets you replace a calendar with evidence, and it is also what lets you prove availability to your own asset management function.

How to add communications to an EcoVAR

Physical provisions

Every EcoVAR provides:

  • An RJ45 Ethernet data port for the communications device.
  • A DC auxiliary supply, nominally 15 V, 15 W, for powering that device.

The utility selects the communications bearer. In practice this is usually a cellular router where no utility network exists at the site, or a connection into an existing utility WAN, fibre or mesh where one does. Because the EcoVAR supplies the router, no separate supply, meter or service connection is required. The communications device is powered from the asset it is monitoring.

Three communications paths

PathWhat it delivers
DNP3Integration into conventional SCADA and ADMS platforms. LV measurements and status appear in the system your control room already uses, extending SCADA visibility down to individual LV feeders.
ModbusThe same SCADA integration for utilities and RTUs standardised on Modbus. For utilities with mature SCADA and established cyber processes, DNP3 or Modbus is usually the path of least resistance.
Secure APIConnects the unit to EcoFLEET, the EcoJoule fleet management and configuration platform. EcoFLEET aggregates field performance data across the fleet, provides real time dashboards, and handles remote firmware and settings updates.

EcoFLEET is normally hosted within the utility environment, under the utility security controls. EcoJoule can host it for utilities that want an additional service layer, and that arrangement is agreed case by case.

The paths are not mutually exclusive. A common arrangement is DNP3 or Modbus into SCADA for operational monitoring and control, with the Secure API to EcoFLEET for engineering data, fleet analytics and firmware management.

What the data lets you find

Connected LV STATCOMs turn a class of LV faults from customer reported into utility detected:

  • Harmonic sources. Distortion measured at multiple points identifies which section a source sits on.
  • Blown LV fuses and open neutrals. These appear immediately as a phase level anomaly.
  • Voltage excursions and flicker. With waveform evidence attached, rather than a description over the phone.

Historically the first indication of most of these was a customer complaint, which means the problem had already persisted long enough for someone to be affected by it, and long enough for the evidence to be gone by the time a crew arrived. A connected EcoVAR reports the condition when it occurs.

The commercial case in one line

The hardware provision is already in the unit. The incremental cost of connecting an EcoVAR is a communications device and its data plan. What you get in return is a settings change that costs nothing instead of a truck, LV data you have not previously been able to buy at this resolution, and a maintenance programme driven by condition rather than calendar.

If you have EcoVARs in service without communications, we can scope the retrofit against your existing units. If you are planning a deployment, the time to specify the communications path is now, while the installation is still on paper.

References on Conservation Voltage Reduction

  • US EPA / ENERGY STAR, Voltage Optimisation and CVR: Evaluation, Measurement and Verification Best Practice.
  • Diaz-Aguilo et al., Field Validated Load Model for the Analysis of CVR in Distribution Secondary Networks, IEEE Transactions on Power Delivery.
  • Padullaparti et al., Conservation Voltage Reduction with DERMS, Grid Edge and Legacy Devices, NREL, 2023.
  • Assessment of Conservation Voltage Reduction in Distribution Networks with Voltage Regulating Distribution Transformers, Energies 16(7), 2023.
  • Estimation of Conservation Voltage Reduction Factors Using Measurement Data of the KEPCO System, Energies 10(12), 2017.

EcoJoule Completes First Export To Portugal

EcoJoule Energy has completed the first export of its EcoVAR low-voltage distribution STATCOM to Portugal, opening a new European market for the Australian manufacturer.

The 40 kVAR three-phase units were built at the company’s Brisbane facility and dispatched this month. With the sale, EcoVAR technology is now in service across four continents — Oceania, Asia, the Middle East and Europe.

The export milestone follows a $15 million capital raise EcoJoule completed in 2025, led by Ellerston Capital and Fifth Estate Asset Management, and including a $3 million commitment from the Clean Energy Finance Corporation (CEFC) through its Powering Australia Technology Fund.

The investment has supported EcoJoule to build manufacturing capacity, inventory and its commercial team, the foundations for meeting demand at home and, increasingly, overseas.

“We backed EcoJoule through the Powering Australia Technology Fund to help a market-leading Australian technology company scale up and get its grid solutions to more customers. Seeing that technology now exported to Europe shows Australian clean energy innovation competing on the world stage, and at the same time helps networks here at home and abroad integrate more renewable energy.”
— Malcolm Thornton, Head of Growth Capital, CEFC
Tweet

The EcoVAR is a low-voltage distribution STATCOM. It supplies dynamic reactive power, balances load across phases and filters harmonics directly on the distribution network.

It installs without a network outage, and helps distributors hold voltage within limits and connect more rooftop solar to existing feeders, deferring or avoiding conventional network augmentation.

“I started EcoJoule after seeing, at a utility, how quickly rising solar exports push voltage outside limits on the low-voltage network. The EcoVAR was designed to correct that at the point where it occurs, without taking customers off supply. The CEFC backing has helped us take that technology from Australia to the world.”
— Dr Mike Wishart, Founder, EcoJoule Energy
Tweet

Dr Wishart developed the EcoVAR after observing voltage problems firsthand while working at an electricity utility, drawing on a career formerly leading research and development for global multinational electrical companies.

“Portugal is the newest market to adopt the EcoVAR, and it shows technology designed and built in Australia is competitive globally. With CEFC’s support behind our scale-up, our task is to keep making it straightforward for networks anywhere to access it.”

“Portugal is the newest market to adopt the EcoVAR, and it shows technology designed and built in Australia is competitive globally. With CEFC’s support behind our scale-up, our task is to keep making it straightforward for networks anywhere to access it.”
— Martin van der Linde, Chief Commercial Officer, EcoJoule Energy
Tweet

Mr van der Linde recently joined EcoJoule as Chief Commercial Officer to lead the company’s global market development.