EcoLVPlanner is a web-based planning tool for low voltage distribution feeders. It runs an unbalanced three-phase load flow, reports voltage, unbalance, loading and hosting capacity, and calculates where an EcoVAR LV STATCOM will resolve voltage violations. The network builder, load flow and EcoVAR placement are available for utility engineers on request – accessible at https://portal.ecojoule.com
What the load flow reports
The solver models each phase and the neutral separately, so it shows the effects that a balanced model hides: phase voltages diverging along the feeder, neutral current, and voltage unbalance from single-phase loads and solar. Each run reports:
Voltage: minimum and maximum phase voltage, and the buses outside the limits of the selected voltage standard
Unbalance: voltage unbalance factor at each bus, against a 2% limit
Loading: transformer and conductor loading as a percentage of thermal rating, and neutral current
Profiles: per-phase voltage against distance from the transformer, and a per-bus results table
Time Domain: Run time-domain analysis of 24 hours or a year to consider seasonal impacts and load changes
Studies run as a single operating point (snapshot) or across a 24-hour load and generation profile (time series).
Workflow
Build the feeder. Place the transformer source, buses, loads, PV, capacitors and EcoJoule devices on the canvas. Set conductor length and impedance per kilometre, and assign phases to each load. Load profiles import from CSV. Alternatively, an AI prompt is included for utilities to convert their data into compatible JSON in their controlled internal environment. This JSON can be pasted into the tool and render the network.
Run and review. The network map colours each bus by voltage, unbalance, loading or neutral current. Select a bus to see its phasor diagram and Thévenin impedance.
Place an EcoVAR. The tool calculates the location and number of EcoVARs that bring the feeder within limits, then reruns the load flow to show the before-and-after result.
Check hosting capacity. Compare the solar hosting capacity of the feeder with no equipment, with an EcoVAR and with an EcoSTORE.
Export. Save the case file to share or revisit, or export a PDF report of the results.
How EcoVAR placement is calculated
The tool selects the electrically weakest bus at or upstream of the voltage violations. A device there supports its own bus and every bus downstream of it, so it clears the most violations per kVAr. The tool reports the X/R ratio seen at that bus, which indicates how effective reactive support will be. EcoVAR Volt-VAR settings and active power phase balancing can be set per device and rerun.
Hosting capacity is found by adding balanced PV uniformly across the feeder until the worst bus reaches the upper voltage limit (253 V under AS 60038). It is a planning indicator for comparing options, not a connection assessment.
Limits
EcoLVPlanner is a planning model. Its results depend on the conductor, load and generation data entered, and will deviate from field measurements. Comparing model results with measured data on your own network quantifies that deviation and improves later studies. The tool is hosted by EcoJoule and has no connection to installed EcoVAR or EcoSTORE units.
Requesting access
Utility engineers can access EcoLVPlanner at https://portal.ecojoule.com Access can be requested at sales@ecojoule.com
An Unbalanced Network corrected with an EcoVAR Placement in EcoLVPlanner
EcoJoule Energy is helping Victorian households make better use of rooftop solar following the successful installation of ten pole-mounted neighbourhood batteries across AusNet’s electricity distribution network.
The batteries, delivered as part of the Victorian Government’s 100 Neighbourhood Battery Program, are now operational across ten Victorian communities, supporting 1,777 households and helping create a smarter, more flexible electricity network.
Developed by EcoJoule Energy, the pole-mounted EcoSTORE battery energy storage systems capture excess rooftop solar generation during the day and release stored energy back into the local electricity network when demand increases, particularly during the evening peak.
The installations are located in Coldstream, Diamond Creek, Ferntree Gully, Heathmont, Knoxfield, Lysterfield, Smiths Beach, Traralgon, Wantirna and Wantirna South.
EcoJoule Energy co-founder and CEO Dr Mike Wishart said the project demonstrated the important role distributed battery storage could play in addressing the challenges created by Australia’s rapid uptake of rooftop solar.
“Australia has led the world in rooftop solar adoption, but our electricity networks were never designed to manage large volumes of electricity flowing back into the grid from individual households,” Dr Wishart said.
“By installing battery storage directly into the low-voltage network, we can capture more of that locally generated renewable energy and make it available when households need it most.
“This is a practical example of how Australian-developed technology can help electricity distributors unlock more value from existing infrastructure while supporting the transition to renewable energy.”
The compact batteries, approximately the size of a bar fridge, are installed on existing electricity poles in areas with high levels of rooftop solar generation.
According to AusNet, the batteries can collectively supply enough electricity to power up to 50 homes for two hours after sunset under normal network operating conditions.
The installations also help maintain consistent voltage levels for more than 100 surrounding homes, creating opportunities for additional rooftop solar connections, household electrification and electric vehicle charging.
AusNet General Manager Strategy & Regulation Charlotte Eddy said the batteries were helping communities make better use of locally generated renewable energy.
“The batteries act like miniature energy banks, storing solar energy during the day and making it available later, helping manage peak electricity use in the local area and creating capacity for more rooftop solar and household electrification,” Ms Eddy said.
The installations form part of a broader shift towards distributed energy storage, which allows electricity distributors to manage local network constraints without relying exclusively on traditional network upgrades.
EcoJoule Energy’s EcoSTORE technology has been designed specifically for deployment within low-voltage electricity networks, combining battery storage with advanced power electronics and network management capabilities.
Unlike large-scale battery installations connected to transmission or high-voltage distribution networks, pole-mounted systems can be deployed close to where electricity is generated and consumed.
Dr Wishart said the ability to manage energy storage and voltage at a local level would become increasingly important as more households installed solar panels, batteries and electric vehicles.
“The energy transition is changing how electricity moves through our networks. Instead of electricity flowing in one direction from large generators to customers, we now have millions of households generating, storing and consuming electricity at different times,” he said.
“Technologies such as EcoSTORE give network operators additional flexibility to manage these changes while maintaining reliable electricity supply.
“Importantly, they can also help create the network capacity needed to accommodate more renewable energy without the cost and disruption of major infrastructure upgrades.”
AusNet said the project would also help it reassess areas where solar exports are currently constrained, potentially allowing more households to export additional electricity into the network.
Dr Wishart congratulated AusNet and the Victorian Government on the successful rollout.
“We’re extremely proud to see EcoJoule technology supporting Victorian communities and delivering real benefits to households and the electricity network,” he said.
“Projects like this demonstrate what can be achieved when innovative Australian technology is combined with forward-thinking network operators.
“We look forward to building on this success and helping more communities across Australia and internationally benefit from smarter, more flexible electricity networks.”
The Victorian installations add to EcoJoule Energy’s growing portfolio of distributed energy technology projects in Australia and overseas.
Queensland-based energy technology company EcoJoule Energy has been recognised for its innovative solutions to electricity network challenges, winning the Innovation – Challenger Award at the 2026 Australian Financial Review Energy Awards.
The award recognises businesses helping shape the future of Australia’s energy industry through innovation, excellence and achievement.
The recognition marks another milestone for EcoJoule, which has spent more than a decade developing technologies that help electricity networks accommodate growing rooftop solar generation, electric vehicles and other distributed energy resources.
EcoJoule’s flagship EcoVAR technology provides dynamic voltage regulation and phase balancing, while its EcoSTORE battery energy storage systems help improve network reliability and flexibility.
“We’re the first ones out the gate, so we’re very lucky in that regard,” Dr Wishart told the AFR.
He said EcoJoule offered electricity networks a more affordable alternative to traditional infrastructure upgrades.
“Probably our biggest competitor would be power companies upgrading their networks, but we give them an option that is much cheaper than replacing poles and wires.”
The AFR also highlighted EcoJoule’s growing international footprint, with its technology distributed across 10 countries and increasing demand from the United Kingdom, Europe and South-East Asia.
Dr Wishart said the award reflected the dedication of EcoJoule’s employees and supporters.
“I’m incredibly grateful to our talented team, whose hard work, expertise and determination have made this possible. I also want to thank our customers, partners, investors and everyone who has supported us along the way.
“We’ve achieved a great deal together, but with growing demand for our technology around the world, I genuinely believe this is only the beginning.”
EcoJoule is now focused on accelerating its international expansion and demonstrating how Australian-developed technology can help electricity networks worldwide navigate the energy transition.
EcoJoule uses lithium iron phosphate (LFP) cells in its battery energy storage systems. This bulletin sets out the fire-relevant differences between LFP and lithium nickel manganese cobalt oxide (NMC) cells, and the protection layers the EcoSTORE adds on top of cell chemistry.
What the data shows
Compared with NMC, LFP cells:
release negligible oxygen when the cathode breaks down, so the cell does not feed its own fire
reach a lower peak temperature and release heat more slowly, making cell-to-cell propagation less likely and slower
begin thermal runaway at a higher temperature, giving more margin before a fault becomes self-sustaining
contain no nickel or cobalt, and have a longer cycle life
LFP has lower energy density than NMC. For stationary network equipment, weight and volume are secondary to safety and service life, so this trade-off favours LFP.
LFP Key figures
Negligible
Oxygen released by LFP cathode on breakdown NMC: releases oxygen
350–650 °C
LFP peak cell temperature in runaway NMC: 550–900 °C
220–250 °C
LFP thermal runaway trigger temperature NMC: 150–220 °C
None
Nickel or cobalt in LFP cells NMC: both
Why this matters on the distribution network
Distribution-connected batteries sit on poles, footpaths and road reserves, close to homes and the public, and are usually unattended. The consequence of a fire at these sites is high, so EcoJoule reduces the likelihood of one at the source by selecting LFP.
LFP is not non-combustible.
Its electrolyte and vent gas are flammable. Cell chemistry is the first layer of protection in the EcoSTORE, not the only one. The layers that follow it are set out here.
Fire-relevant characteristics of NMC and LFP
Characteristic
NMC
LFP
Relevance
Cathode structure [4]
Layered metal oxide
Olivine phosphate with strong phosphorus–oxygen bonds
Determines thermal stability of the cathode
Oxygen release on cathode breakdown [4]
Yes. Released oxygen supports combustion inside the cell
Negligible
Oxygen release makes an NMC fire self-sustaining and difficult to suppress
Thermal runaway trigger temperature* [2,3,11]
Approx. 150–220 °C, lower for high-nickel variants
Approx. 220–250 °C
Higher trigger temperature gives more margin before runaway becomes self-sustaining
Peak cell temperature in runaway* [1,5,11]
Approx. 550–900 °C
Approx. 350–650 °C
Lower peak temperature reduces heat transfer to adjacent cells
Rate of heat release [3,9]
High
Low to moderate
Governs the speed of escalation
Cell-to-cell propagation [2,4]
More likely and faster
Less likely and slower
Propagation turns a single-cell fault into a module or system fire
Vent gas [6,7,8]
Larger volume per Ah, flammable, CO-rich
Smaller volume per Ah, flammable, H2-rich, with a lower flammability limit
Unignited gas can accumulate, so enclosure ventilation and deflagration management are required for both. Vent gas from both is toxic
Cell energy density* [10]
Approx. 190–275 Wh/kg
Approx. 140–205 Wh/kg (current cells)
Lower density is acceptable in stationary network equipment
Cycle life
Lower
Higher
Supports long-life network assets
Nickel and cobalt content
Yes
No
Supply-chain and end-of-life considerations
* Indicative ranges from the references below. Actual values depend on cell format, state of charge, age and manufacturer. Trigger temperature is the point at which runaway becomes self-sustaining; measurable self-heating begins earlier, at approx. 90–110 °C for NMC and 150–170 °C for LFP [12].
How the EcoSTORE manages the residual risk
Pole-mount EcoSTORE units apply eight protection layers. Layers 3 and 4 act independently of each other, so a single failure does not remove thermal protection [13].
Layer
Mechanism
Effect
1 Cell chemistry
LFP cells (Table 1)
Lowers the likelihood of thermal runaway and of propagation between cells
2 Cell temperature monitoring
The BMS measures the temperature of every cell and reports it to the inverter
Cell-level thermal data for both protection layers below
3 Inverter derating
Battery current ramps down linearly from full output at 45 °C to zero at 60 °C
Charge and discharge current is removed before cells reach 60 °C
4 BMS disconnection
The BMS independently disconnects the batteries above 65 °C, the cells’ rated limit
Second, independent thermal protection
5 Module fusing
Fuses in each battery module open under short circuit
Removes a battery short circuit and arc flash as an ignition source
6 Cell pressure vents
Each cell has a designed vent that opens above a set internal pressure
Releases gas before cell pressure reaches a hazardous level
7 Thermal management
Fans draw air in at the base, across the modules and out through side vents. Heat shields with a convective air gap cover the enclosure
Holds enclosure temperature close to ambient and limits solar heating
8 Enclosure
AISI 304 stainless steel. A 4 mm back shields the pole. The inverter sits in a separate cabinet.
Improved containment under unlikely failure mode. Separates a battery event from the pole and the inverter
Safe approach guidance
EcoJoule recommends that network operators build the following checks into safe-work procedures before crews access an operating EcoSTORE [13]:
Review the unit’s recorded temperatures for the previous 24 hours for abnormal readings.
Inspect from a distance for smoke or flame at the exhaust vents, heat haze above the unit, or distorted panels.
From at least 3 m, measure the enclosure surface temperature on at least two sides with an infrared thermometer, then act on the result:
Surface temperature
Action
Below 75 °C
Safe to approach. Wear gloves when opening or handling panels
75–100 °C
Risk of burns on contact. Wait at least 30 minutes, re-measure and reassess
Above 100 °C
Treat as unsafe and a possible thermal event. Confirm the unit is isolated from the grid, set an exclusion zone, post observers to prevent approach, and complete a risk assessment before any further action
ABOUT ECOJOULE ENERGY
EcoJoule Energy designs and manufactures low-voltage grid-edge power electronics in Brisbane, Australia. Its EcoVAR LV D-STATCOM is in field service with distribution utilities in Australia and internationally, and is available in pole-mount (EcoVAR Alto) and ground-mount (EcoVAR Terra) variants. EcoJoule’s technology relieves grid congestion and increases network hosting capacity, allowing the benefits of the energy transition to reach more users of the existing distribution network.
References
[1] Golubkov A.W. et al., “Thermal-runaway experiments on consumer Li-ion batteries with metal-oxide and olivin-type cathodes”, RSC Advances 4 (2014) 3633–3642. https://doi.org/10.1039/C3RA45748F [2] “Thermal and mechanical safety assessment of type 21700 lithium-ion batteries with NMC, NCA and LFP cathodes – investigation of cell abuse by means of accelerating rate calorimetry (ARC)”, Batteries 9(5) (2023) 237. https://doi.org/10.3390/batteries9050237 [3] “Comparison on thermal runaway and critical characteristics of cylindrical lithium-ion batteries: a review”, ACS Chemical Health & Safety. https://doi.org/10.1021/acs.chas.4c00121 [4] “Thermal runaway propagation in automotive lithium-ion batteries with NMC-811 and LFP cathodes: safety requirements and impact on system integration” (2023). https://www.sciencedirect.com/science/article/pii/S2590116823000802 [5] “Evaluation of the laminar burning velocity of various battery vent gases emitted during the thermal runaway of Li-ion cells” (2025). https://www.sciencedirect.com/science/article/pii/S0950423025001159 [6] “NVPF sodium-ion versus NMC and LFP lithium-ion batteries in thermal runaway: vent gas composition and thermal analysis”, Batteries 11(9) (2025) 323. https://www.mdpi.com/2313-0105/11/9/323 [7] “Review of gas emissions from lithium-ion battery thermal runaway failure — considering toxic and flammable compounds”, Journal of Energy Storage (2024). https://www.sciencedirect.com/science/article/pii/S2352152X24008739 [8] “Thermal runaway characteristics and gas composition analysis of lithium-ion batteries with different LFP and NCM cathode materials under inert atmosphere”, Electronics 12(7) (2023) 1603. https://www.mdpi.com/2079-9292/12/7/1603 [9] “Thermal runaway characterization of cylindrical lithium-ion and sodium-ion batteries with various sizes and energy contents”, Journal of Power Sources (2025). https://www.sciencedirect.com/science/article/pii/S0378775325010766 [10] PowerUp / CEA-Liten, “NMC vs LFP: safety and performance in operation” (2025). https://powerup-technology.com/nmc-vs-lfp-safety-and-performance-in-operation/ [11] Electric & Hybrid Vehicle Technology International, “LFP vs NMC thermal runaway” (2025). https://www.electrichybridvehicletechnology.com/technical-articles/lfp-vs-nmc-thermal-runaway.html [12] Battery Design / Akkuracy Battery Testing, “Objective safety analysis of NMC vs LFP” (2026). https://www.batterydesign.net/objective-safety-analysis-of-nmc-vs-lfp/ [13] EcoJoule Energy, “EcoSTORE battery fire / explosion risk reduction and mitigation” (2023). Available on request.
The EcoVAR runs Volt-VAR droop and active power phase balancing at the same time. A priority setting decides which control gives way when a phase reaches its rating. Matching that setting to the X/R ratio of the network gets more correction from the same unit.
Two controls, one rating
Volt-VAR droop. Each phase injects capacitive VARs when its voltage is low and absorbs inductive VARs when it is high, with a configurable dead band around nominal. All three phases share one droop curve but respond to their own measured voltage, so one phase can inject while another absorbs.
Active power phase balancing. The EcoVAR draws active power from the high-voltage (lightly loaded) phase and returns it to the low-voltage (heavily loaded) phases. It has no energy store, so the three phase active powers always sum to zero. Phase voltage is the proxy for phase loading, so no series CTs are needed. Balancing also reduces neutral current back to the transformer.
Control
Corrects voltage unbalance
Corrects average voltage
Volt-VAR droop (Q)
Yes, per phase
Yes
Active power balancing (P)
Yes
No: P₁ + P₂ + P₃ = 0
If all three phases are high, for example during midday solar export, active power balancing cannot lower them. Only reactive power absorption can.
Priority modes and when to use them
Both controls run continuously. The priority setting acts only when a phase reaches its apparent power limit, and decides which control is curtailed.
Setting
Capacity first to
Remaining capacity to
Suited to
Q-Priority
Volt-VAR droop
Phase balancing
Reactive networks (higher X/R): overhead feeders with a significant reactive component; open wire overhead
Where X dominates, a VAR moves voltage further than a watt. Where R dominates, a watt moves voltage further than a VAR. P-Priority is most effective where low X/R coincides with significant phase imbalance, such as single-phase rooftop solar or EV charging concentrated on one phase.
The priority can be changed remotely through the EcoFLEET™ Fleet Manager after commissioning. Parameter details are in section 5.4 of the EcoVAR User Manual.
We are often asked what an EcoVAR does when it loses one or more phases of supply, and whether it can keep a de-energised line alive. It cannot.
The EcoVAR has no battery. It is three single-phase STATCOMs, one per phase, sharing a DC bus. That bus is a capacitor bank charged from the grid. It lets the EcoVAR move power between phases and supply reactive power, but it is not an energy source.
If any phase is lost, the EcoVAR stops compensating on all three phases and opens its grid relays. While the other phases stay energised, the controller remains on, so the event is logged and the unit can still be reached remotely. If all phases are lost, the unit powers down. Once supply returns and has been stable for the set reconnection delay, the unit reconnects automatically.
Short sags from motor and heat pump starts are handled differently. The EcoVAR injects maximum capacitive reactive power within 10 ms of phase voltage falling below 180 V, and holds this for up to 4 seconds by default. If the sag lasts longer, the unit trips and disconnects as it would for a lost phase. Protection settings follow AS/NZS 4777.2:2020 by default and can be changed for other standards. The rest of this bulletin sets out the detail.
Architecture
The EcoVAR converts 230 V phase-to-neutral AC to about 800 V DC on a capacitor bus shared by the three phase converters. The shared bus is what allows active phase balancing: power drawn from a lightly loaded phase is delivered to a heavily loaded one. Net active power exchange with the network is limited to conversion losses. The capacitors hold enough energy to control current, not to supply load.
Figure 1. EcoVAR power architecture. Three phase-to-neutral converters share one DC bus (neutral omitted for simplicity). Battery terminals are fitted for a future EcoSTORE upgrade and are unused in a standalone EcoVAR.
The EcoVAR is sometimes confused with the EcoSTORE, which adds battery storage to the same inverter platform. A standalone EcoVAR has no battery connected.
Operating states
State
Grid relays
Controller
Compensating
Typical trigger
Running
Closed
On
Yes
Normal operation: voltage regulation, phase balancing, harmonic filtering
Standby
Closed
On
No (IGBTs off)
Ready to operate, or compensation disabled
Waiting
Open
On while any phase is energised
No
After a trip or grid disturbance, until reconnection conditions are met
Powered down
Isolated by breaker or fuse
Off
No
Manual isolation, or loss of all phases
Whenever the controller is powered, the unit logs data and can be configured and interrogated remotely through EcoFLEET, which displays these state names.
Sag ride-through
A fast-acting control loop (10 ms time constant) overrides the slower Volt-VAR droop control (5 s time constant). When phase voltage falls below the sag threshold, that phase injects maximum capacitive reactive power to reduce the depth of the dip. This covers common sags from motor starts, heat pumps and air-conditioner compressors.
Parameter
Default
Range
Voltage sag/swell mitigation
Disabled
On / Off
Sag threshold
180 V
150–230 V
Undervoltage delay (maximum capacitive injection)
2 s
0–4 s
Swell threshold
265 V
230–265 V
Overvoltage delay (maximum inductive absorption)
1 s
0–2 s
If the sag clears within the delay, the unit carries on. If it persists, the unit trips and moves to Waiting.
Loss of one or two phases
A lost phase is detected as a sustained undervoltage on that phase:
Below 70 V: immediate trip and disconnection.
Held between 70 V and 180 V, for example by downstream load or PV on an open conductor: trip after the undervoltage delay.
Unintentional island: the frequency-shift active anti-islanding function disconnects the unit within 2 seconds.
Why the whole unit trips, not just the lost phase.
Firstly, inverter grid connection standards like AS/NZS 4777.2 mandate that all phases should trip when any one phase is lost. Although it is debateable whether PV inverter and BESS standards like AS/NZS 4777.2 are directly applicable to a STATCOM like the EcoVAR, these grid connection standards have become an industry norm, so EcoJoule has ensured compliance with them. Secondly, from a technical viewpoint active phase balancing uses all three phases together. If the two healthy phases kept running, the balancing control would draw power from them through the DC bus to try to hold up the dead phase. That would load the healthy phases and could energise the lost one. Tripping all three phases prevents both.
In Waiting, the relays are open and the unit does not inject onto any phase. The controller stays powered from the healthy phases, so the event is recorded and can be reviewed remotely.
Loss of all phases
With no supply, the controller loses power and the unit shuts down. The EcoVAR has no stored energy source and cannot energise the network.
Default protection limits
Protective function
Limit
Trip delay
Maximum disconnection time
Undervoltage 2 (V<<)
70 V
1 s
2 s
Undervoltage 1 (V<)
180 V
10 s
11 s
Overvoltage 1 (V>)
265 V
1 s
2 s
Overvoltage 2 (V>>)
275 V
–
0.2 s
Under frequency (F<)
47 Hz
1 s
2 s
Over frequency (F>)
52 Hz
–
0.2 s
AS/NZS 4777.2:2020 Tables 4.1 and 4.2 (Australia A). Alternative settings, for example to IEEE 1547 or EN 50549, are available on request.
If a voltage excursion clears before the trip time, the unit returns to its previous operating point within 400 ms of voltage recovering.
Reconnection
After a trip, the unit reconnects automatically once voltage and frequency have stayed within limits for the grid connection delay. Range: 5–360 s.
For field crews
The EcoVAR is not a generation source and cannot backfeed an isolated line. Inside the enclosure, the DC link capacitors can potentially hold lethal voltage for up to 10 minutes after power-down. Treat the unit as live until it has been metered.
ABOUT ECOJOULE ENERGY
EcoJoule Energy designs and manufactures low-voltage grid-edge power electronics in Brisbane, Australia. Its EcoVAR LV D-STATCOM is in field service with distribution utilities in Australia and internationally, and is available in pole-mount (EcoVAR Alto) and ground-mount (EcoVAR Terra) variants. EcoJoule’s technology relieves grid congestion and increases network hosting capacity, allowing the benefits of the energy transition to reach more users of the existing distribution network.
Why service reallocation and augmentation no longer hold balance on feeders with single-phase EV charging, heat pumps and rooftop PV — and what a three-converter D-STATCOM does differently.
Phase imbalance on low voltage networks is not new. What has changed is the size and behaviour of the loads creating it, and the rate at which a balanced feeder becomes an unbalanced one.
Imbalance is now a load-growth problem
Australian LV distribution is a four-wire multiple earthed neutral system, and almost every domestic connection is single phase. Historically that was manageable: individual loads were small, diversity across dozens of customers smoothed the per-phase totals, and a planner could allocate services across phases at connection and expect that allocation to hold for a decade.
Single-phase 7.2 kW EV chargers, heat pumps, electric hot water, reverse-cycle air conditioning and residential batteries break that assumption. One EV charger can represent more after-diversity demand than the five houses around it. Loads arrive where customers buy them, not where the network has headroom, and they cluster. One street adopts, the next does not. A feeder that measured within a few percent of balance at commissioning can sit 30 to 40 percent out on a winter evening, where the cold climate means that load diversity is simply all feeder heat pumps operating. Conversely, the imbalance moves during the day, as charging, hot water and cooling cycles overlap.
Why imbalance presents as a voltage problem
Unbalanced phase currents return through the neutral. In an MEN system the neutral is not a zero-volt reference; it carries current and develops a voltage along its length. That neutral shift moves the star point relative to the customer connections, so the heavily loaded phase drops further than its own load would explain, and the lightly loaded phases rise. The customer on phase C experiences a voltage complaint caused by loads on phase A.
The loss penalty follows the same currents.
Condition
Phase currents
Neutral current
Conductor loss term
Unbalanced
100 A / 60 A / 40 A
53 A
18,000 A²
Balanced
66.7 A each
0 A
13,333 A²
Same total current delivered, unity power factor, equal phase and neutral conductor resistance. Balancing removes the neutral current and reduces conductor loss by approximately 26 percent.
WORKED EXAMPLE
1. Neutral current is the phasor sum, not the arithmetic sum
Ia = 100 A at 0° Ib = 60 A at −120° Ic = 40 A at +120°
Real = 100 − 30 − 20 = 50.0 A
Imaginary = −51.96 + 34.64 = −17.32 A
|In| = √(50.0² + 17.32²) = 52.9 A
2. Loss term is ΣI² across all four conductors
Unbalanced: 100² + 60² + 40² + 52.9² = 18,000 A²
Balanced: 3 × 66.7² + 0² = 13,333 A²
Reduction: 1 − 13,333 / 18,000 = 25.9%
3. Symmetrical component view
Positive sequence 66.7 A → 13,333 A²
Negative sequence 17.6 A → 933 A²
Zero sequence (phases) 17.6 A → 933 A²
Zero sequence (neutral) 52.9 A → 2,800 A²
Positive sequence is the component doing useful work. The remaining 4,667 A² is the imbalance penalty, and the EcoVAR removes it by cancelling the negative- and zero-sequence components. Figures are conductor loss in the LV section only, at unity power factor with equal phase and neutral conductor resistance; they exclude converter losses. Where the neutral is of reduced cross-section relative to the phases, the penalty is larger than shown.
The distribution transformer is derated by the same mechanism: it reaches its thermal limit on the worst phase, not on its nameplate kVA. Imbalance therefore consumes three things a planner needs — voltage headroom, thermal capacity and network losses. It also consumes hosting capacity, because the same neutral shift that pulls one phase low pushes another high, and rooftop PV on that phase curtails first.
What traditional balancing achieves, and where it stops
Service reallocation. A crew measures the pillar or the transformer over a week, identifies the loaded phase, and moves services across. It works, and it is inexpensive. It also requires a truck, a customer outage and a decision based on a snapshot. The measurement describes last month’s load pattern. The next EV connection, the next hot-water changeover or a shift in occupancy reverses it. Networks that rebalance on complaint are rebalancing the same feeders repeatedly.
Augmentation. A second transformer, reconductoring, or splitting the LV area fixes the peak with certainty. It also costs capital, takes months of design, easement and outage planning, and is sized for a load forecast that single-phase electrification keeps revising upward.
Conventional three-phase STATCOMs. A standard three-leg converter injects a balanced positive-sequence current. It can raise or lower all three phase voltages together, and it can correct power factor, but it cannot differentiate between phases. Applied to an unbalanced feeder it lifts the low phase and the already-high phases with it.
Three converters, one DC bus
The EcoVAR is built as three independent single-phase STATCOM systems sharing a common DC bus. That architecture is the reason it can do something a conventional STATCOM cannot.
Because each phase has its own converter, the units can operate in opposite directions at the same instant. The converter on the heavily loaded phase supplies active power to the network; the converters on the lightly loaded phases absorb it. The shared DC bus is the transfer path. Net real power exchange with the network is close to zero, but the currents drawn from the transformer and the upstream conductor are balanced.
Active power balancing control manages this continuously. There are no discrete steps to select and no transformer taps to move. The device sets per-phase active and reactive current targets from the instantaneous measured condition and holds balance as the load profile changes through the day.
Sub-cycle response and motor starts
The control operates on instantaneous per-phase quantities rather than RMS values averaged over seconds, so correction occurs within a cycle.
This matters most for motor starting. A heat pump or air conditioning compressor draws several times its running current for a few cycles at start. On a weak single-phase connection that inrush produces a visible voltage dip, and through the neutral shift it disturbs the other two phases as well — the sag propagates to customers who did not cause it. A balancer that responds over seconds sees the event only after it has finished.
The EcoVAR supports the starting phase from the DC bus as the current rises, so the dip is contained at its source and does not couple across. The same mechanism handles PV inverter ramps, battery mode changes and EV charger step loads.
What the planner gets
Balanced phase currents at the distribution transformer, held continuously rather than set once.
Neutral current and neutral voltage rise reduced, with the associated loss reduction.
Voltage spread between phases narrowed, recovering headroom for both load and PV export.
Sub-cycle containment of motor starts and step loads.
Installation on an energised network with no customer outage.
Per-phase measurement of the LV condition, available remotely, including after the correction is in service.
Phase imbalance created by single-phase electrification is dynamic. It changes hour to hour and grows year on year. Correction that is set manually, or that responds in seconds, is answering a question the network stopped asking. Dynamic balancing addresses it at the timescale it occurs, on the existing poles and wires.
ABOUT ECOJOULE ENERGY
EcoJoule Energy designs and manufactures low-voltage grid-edge power electronics in Brisbane, Australia. Its EcoVAR LV D-STATCOM is in field service with distribution utilities in Australia and internationally, and is available in pole-mount (EcoVAR Alto) and ground-mount (EcoVAR Terra) variants. EcoJoule’s technology relieves grid congestion and increases network hosting capacity, allowing the benefits of the energy transition to reach more users of the existing distribution network.
EcoJoule Energy’s Network Planners’ Guide explains how D-STATCOM technology provides network planners and engineers with a faster, more flexible and lower-cost alternative to conventional network augmentation, while improving voltage regulation, phase balance and power quality across increasingly complex distribution networks.Download the full guide here.
Executive Summary
Low-voltage electricity networks are under growing pressure from rooftop solar, electric vehicles, electrification and other distributed energy resources (DER), while much of the infrastructure supporting them was designed for a very different energy system.
The resulting overvoltage, undervoltage, phase imbalance, and power quality issues do not always indicate that a network has run out of capacity. Where the constraint is voltage or imbalance rather than thermal capacity, LV D-STATCOM technology such as EcoJoule Energy’s EcoVAR™ can provide a faster, more flexible alternative to traditional augmentation.
EcoVAR can be installed in approximately two hours with no customer outage, avoiding much of the engineering, construction and disruption associated with traditional network upgrades. In the illustrative example examined in this paper, the D-STATCOM solution delivers an annualised cost that is approximately 2.98 times lower than that of traditional augmentation. It can also defer major capital works and be redeployed as network requirements change.
The opportunity is not to replace augmentation where additional thermal capacity is genuinely required. It helps match investment to actual constraints, solve problems sooner, deploy capital more efficiently, and get more from existing network infrastructure.
D-STATCOM or Traditional Augmentation?
Traditional augmentation means reconducting LV lines, installing new transformers, or extending the medium-voltage supply to split feeders and shorten LV runs. Manual phase balancing, moving single-phase customer connections between phases, is also a form of augmentation.
A D-STATCOM is a form of augmentation. It requires no new HV line, no outage, and installation is under two hours. The engineering design is standard for all installations on a given network.
The limitation is explicit: a D-STATCOM does not add thermal capacity. Only augmentation does that.
Most voltage, imbalance and harmonic problems can be resolved without adding capacity. That is the selection test.
Three differences matter to a planner.
1. Speed – Connected in parallel to the existing network. No new spans, no new transformer, no new customer connections. Installed and commissioned in two hours. Augmentation projects run in days or weeks and include a customer outage.
2. Project Cost – The unit cost is comparable to that of a single transformer. The difference is the project around it: engineering design, outage management, traffic management, and construction lead time.
3. Redeployment – When capacity becomes the binding limit, an installed D-STATCOM can be moved. It is not customised to a site. Removal takes 15 minutes, and reinstallation takes two hours. Augmentation is fixed to the site where it is built.
Where a D-STATCOM Applies
A D-STATCOM, such as EcoJoule Energy’s EcoVAR, connects in parallel with the existing LV network and directly addresses voltage imbalance and harmonic problems. The technology is particularly applicable where the network is experiencing:
Overvoltage – Often associated with high levels of rooftop PV exporting onto an LV feeder.
Phase imbalance – Created when load and generation are unevenly distributed across the three phases.
Harmonics – Increasingly relevant as inverter-based and power-electronic devices proliferate.
Undervoltage on one or two phases – Where available capacity exists elsewhere across the three-phase network.
Voltage sags, swells and flicker – Where dynamic voltage support can improve local power quality.
Selection Guide
Observed problem
Outcome
Reason
Overvoltage
Cost a D-STATCOM project
Active power is not the limit, so the device always has authority.
Phase imbalance
Cost a D-STATCOM project
At least one phase carries excess active power. Active phase transfer corrects it.
Harmonics
Cost a D-STATCOM project
Harmonic correction is not limited by active power.
Undervoltage on one or two phases
Cost a D-STATCOM project
A single-phase power limit. Correctable by transfer between phases.
Undervoltage on all three phases
Traditional augmentation project
A thermal capacity limit. A D-STATCOM does not add capacity.
LV network at end of life
Both, in sequence
Install the D-STATCOM to hold power quality while the augmentation is designed, then redeploy it.
Calculating the Benefits
The real cost of solving an LV network constraint extends well beyond the upfront price of the equipment.
Traditional augmentation may deliver infrastructure with an asset life measured in decades, while a D-STATCOM has a shorter life but offers something conventional infrastructure cannot: the flexibility to be removed and redeployed as network needs change.
A simple capital-cost comparison therefore does not compare like with like. A more meaningful approach is to compare the cost of delivering the required network outcome over time.
Equivalent Annual Cost (EAC) provides that comparison by annualising each component according to its cost, expected asset life and discount rate:
EAC = C ÷ [(1 − (1 + r)^-n) ÷ r]
Each project component retains its own asset life, allowing long-life infrastructure, engineering, installation and equipment costs to be assessed consistently. This provides planners with a clearer picture of the long-term economics of each approach rather than focusing solely on initial capital expenditure.
The Value of Deferring Augmentation
The decision is not always D-STATCOM or traditional augmentation. Where additional thermal capacity will eventually be required, a D-STATCOM can address the immediate voltage or phase constraint while allowing major augmentation to occur when that additional capacity is actually needed.
Deferral can postpone significant capital expenditure, potentially move investment into a future regulatory period and provide more time to understand how DER penetration and demand will develop.
Importantly, the investment does not have to become stranded when augmentation eventually occurs. If the D-STATCOM still has useful service life, it can be redeployed to another constrained feeder, extending the value of the original investment.
The objective is not to avoid necessary augmentation. It is to solve today’s constraint efficiently, preserve future options and invest in permanent network capacity when the network actually needs it.
How a D-STATCOM Works
The D-STATCOM is a three-phase power electronic device connected to the LV network in parallel. It is three independently controlled inverter-STATCOMs, one per phase, with a common shared 864V nominal DC bus.
Two control actions run at the same time.
Reactive Injection – The unit exchanges reactive current with the network at the point of connection. The voltage change is approximately: ΔV ≈ Q·X / V, where Q is the injected reactive power, X is the upstream reactance and V is the nominal voltage. The unit works against upstream impedance. More upstream reactance gives more voltage authority.
Active Phase Transfer – The unit moves real power between phases through a shared DC bus. This corrects imbalance directly rather than compensating negative sequence current alone. Active harmonic filtering runs on the same hardware, injecting harmonic current in antiphase.
Expected Voltage Correction
Worked case: 95 mm² aluminium overhead conductor, R ≈ 0.32 Ω/km, X ≈ 0.29 Ω/km, X/R ≈ 1, 1 MVA distribution transformer, 40 kVAr device.
Distance from transformer
Voltage correction
As percentage
500 m
≈ 16 V
4.00%
750 m
≈ 22.5 V
5.60%
Transformer rating has little effect at the feeder end. At 750 m, line reactance is about 95% of total upstream reactance, so a 500 kVA and a 1 MVA transformer give nearly the same result.
Two limits apply. Reactive injection does not correct voltage drop caused by real load current through line resistance. On an underground cable, X/R is lower and correction per kVAr is lower than the figures above.
D-STATCOMs still work in both cases, but the total voltage change per unit may be lower. Multiple STATCOMs can be connected to the same LV network to increase power if necessary. It is rare, even on aerial bundled conductor (ABC) networks, to need more than one 40 kVAr unit per LV feeder.
Site Selection
Place the unit near the voltage or imbalance problem. Most installations fall between 50% and 80% of the way along the LV feeder, but that range is a guide rather than a rule. Position follows the problem.
Move toward 50% where PV generation is concentrated in the middle of the feeder, or where the LV line can be backfed. Move toward the far end where the deviation is worst at the end. A shift of a few spans either direction makes no material difference to the result.
Within that zone, select the cheapest site to build. Where the electrically preferred pole carries streetlighting, fuses or telecommunications equipment, or where vegetation restricts access, move to the next clean pole. Installation cost dominates the difference; electrical position does not.
Where smart meter data is available, use it to identify the spans and phases with the most frequent and most severe deviations. This reduces selection to a short list of candidate poles.
Voltage is held closest to setpoint at the point of connection, but the effect is seen along the whole feeder.
A head-end tap changer translates the entire profile: it can be set for midday or for evening, not both. A D-STATCOM at the constrained node holds that node at setpoint and reverses between absorbing and injecting as conditions change.
Connecting a D-STATCOM to the Network
The unit connects in shunt. The feeder continues to carry its load and does not need to be de-energised to connect or remove the unit. There is no customer outage.
Every shunt connection needs overcurrent protection and a means of isolation. Three arrangements are used. All three perform identically. The choice is a work practices decision, not a technical one.
Arrangement
Isolation method
When it is used
Outdoor fuses
Pull the fuses
Lowest cost, fewest components. Not available where technicians may not pull live LV fuses.
Switchboard with circuit breaker
Open the breaker
Where live fuse pulling is prohibited by work practices.
Switchboard with breaker, backup fuses and SPD
Open the breaker
Where surge protection is required by network standard.
Rating is 100 A, whether fuse or breaker. Rated current is 63.5 A continuous, with short-time capability of 1.5 × rated, approximately 95 A. Most off-the-shelf MCBs derate at elevated ambient temperature. At the unit’s 50°C maximum, a marginally sized breaker can trip at full output. A 100 A device holds margin above the derated threshold while remaining low enough to protect the connection. Confirm that the shunt connection conductors are rated to carry 100 A.
Notes for Protection Engineers
The D-STATCOM is not an energy storage device. It sources power from the line side. Loss of phase or loss of supply removes it from the circuit.
Onboard capacitors discharge over approximately one minute on loss of mains.
The protective device on the overhead connection is 100 A, fuse or MCB, subject to work practices.
Anti-islanding is handled by internal relays. Undervoltage and underfrequency disconnect settings are configurable and are shipped to IEC 62477 inverter settings.
As a utility-grade device, the disconnect range is often widened on commissioning. This allows the unit to correct voltage during a sag rather than disconnecting, and to connect to a non-compliant voltage and then bring it into compliance.
The tests highlighted in this white paper are intended to be run by the planner on network data and cost data that the planner controls.
A D-STATCOM will not suit every site. Where the constraint is thermal, it does not apply. Where it does apply, the annualised cost comparison should be run and recorded either way.
For More Information
Martin van der Linde Chief Commercial Officer EcoJoule Energy Pty Ltd sales@ecojoule.com
How the two simultaneous control loops in a three-phase LV STATCOM work, and what each one can and cannot correct.
1. Summary
The EcoVAR uses three independently controlled single-phase inverter stages connected to one shared DC bus.
A Volt-VAR droop curve sets reactive power as a function of measured voltage. The EcoVAR evaluates that curve against each phase voltage separately, so one phase can absorb VArs while another injects them.
A second loop, Active Power Balancing, runs at the same time. It moves real power from lightly loaded phases to heavily loaded phases through the shared DC bus.
The two loops correct different things. Reactive power shifts each voltage as well as the average voltage; active power transfer corrects the difference between phases and reduces neutral current. Neither substitutes for the other.
Both loops operate from voltage measurement only. No series current transformers are required, so installation does not depend on breaking the conductor.
2. What a Volt-VAR droop curve does
A Volt-VAR droop curve is a piecewise-linear rule that converts a measured voltage into a reactive power command. It is defined by four voltage set points and applied continuously, without operator intervention or a network communications link.
Below the lower set point the STATCOM sources reactive power (capacitive operation), which raises voltage at the point of connection. Above the upper set point it sinks reactive power (inductive operation), which lowers voltage. Between the two inner set points the output is zero. That deadband stops the unit from responding to normal small voltage variations.
The EcoVAR follows the generator sign convention: a positive reactive power reference is capacitive (sourcing VArs), a negative reference is inductive (sinking VArs). The characteristic is as described in AS/NZS 4777.2:2020 and similar international standards like EN50549, with leading and lagging slopes that can be set symmetrically or asymmetrically.
Figure 1 — Volt-VAR droop characteristic. Set points shown are an example only.
3. Configurable set points
All four set points are user-configurable from the EcoVIEW engineering tool or by uploading a settings file through EcoFLEET Manager. A limited set is also available over DNP3 and Modbus.
Set point
Range
Function
V1
180 – 225 V
At and below V1 the phase holds maximum capacitive output.
V2
185 – 250 V
Lower edge of the deadband. Capacitive output falls linearly from V1 to zero at V2.
V3
185 – 260 V
Upper edge of the deadband. Inductive output starts here.
V4
190 – 277 V
At and above V4 the phase holds maximum inductive output.
Rated output is 40 kVAr total, 13.33 kVAr per phase, available in both directions across 210 V to 277 V. The unit continues to operate down to 180 V at a maximum continuous 63.5 A per phase, and tolerates connection to any voltage from 0 V to 280 V without damage.
4. Three inverter stages, one DC bus
The EcoVAR is not a single three-phase bridge producing a balanced output. Each phase is served by an inverter stage with its own current control loop, and all three stages are connected to a common DC bus. Two consequences follow directly from that architecture.
First, each stage can be commanded independently. The droop curve is evaluated three times each control cycle, once per phase, against that phase’s own measured phase-to-neutral voltage. One phase reaching its current limit does not constrain the other two.
Second, active (real) power can be moved between phases. Because the three stages share a DC bus, power drawn from one phase can be injected into another without a battery and without any net exchange of energy with the network.
Figure 2 — Active power transfer between phases through the shared DC bus.
5. A single characteristic, three independent evaluations
The three phases share one droop characteristic — the same four set points and the same slopes apply to all of them. What is independent is the input and the output, not the configuration. Each stage measures its own phase voltage and produces its own reactive power command from the shared curve.
This is what allows the EcoVAR to reduce voltage unbalance rather than simply shift the whole voltage profile. On a feeder where L1 sits at 252 V under high PV export and L3 sits at 228 V under load, the same curve puts L1 into full inductive operation and L3 into capacitive operation at the same instant.
The unit can alternatively be configured to act on the average of the three phase voltages. That mode is available for networks whose standards require it, but it gives a poorer voltage outcome for customers and is not the recommended setting.
6. The second loop: Active Power Balancing
Reactive power alone corrects voltage well on reactive networks. On resistive LV networks — underground cable, long aluminium mains, heavily loaded urban feeders — voltage responds more strongly to real power than to reactive power, and reactive injection alone cannot bring the phases together.
Active Power Balancing addresses this. The EcoVAR takes the three phase voltages as a proxy for phase loading: a higher voltage implies a lighter load, a lower voltage implies a heavier one. It then transfers real power from the lighter phases to the heavier ones in proportion to the voltage differences, subject to the constraint that the three phase powers must sum to zero. This reduces current unbalance on the feeder and neutral current at the transformer.
Using voltage as the proxy avoids series current transformers. That removes both the cost and the outage that a CT installation would otherwise require.
Two modes are provided. Gain-based transfer injects real power per phase in proportion to the deviation from the average voltage, with a user-selected P or Q priority that determines which is curtailed first if a phase reaches its apparent power limit. Optimal X/R computes a reference apparent power per phase from a voltage droop and then splits it into active and reactive components according to the source impedance X/R ratio, which is taken from the network model or estimated at commissioning. Active Power Balancing is disabled by default and is enabled per site.
7. Why both loops are needed
The two loops are subject to different constraints, and that is the whole reason for running them together.
Volt-VAR droop (Q)
Active power balancing (P)
Quantity controlled
Reactive power per phase
Active power transfer between phases
Network constraint
Limited only by the per phase apparent power rating of the unit
Sum of the three phase powers must be zero
Effect on average voltage
Can raise or lower all three phases together
None — the three voltage changes sum to zero
Effect on unbalance
Reduces it, most effectively on reactive networks
Reduces it, most effectively on resistive networks
Effect on neutral current
Indirect
Direct reduction at the transformer
Default state
Enabled
Disabled — enabled per site
If all three phase voltages are high, transferring real power between them cannot bring any of them down, because whatever one phase gains another must lose. Only reactive power can move the average. Conversely, on a resistive feeder with one badly loaded phase, reactive power struggles to close the gap and real power transfer does it efficiently. Running both loops covers both cases across the full range of LV network impedances.
8. Control loop timing
Function
Response
Internal current control loop
10 – 90% rise and fall in 2 ms or less
Volt-VAR droop response (ramp-rate limited)
Default 5 s, to keep the steady-state response smooth. However, can be set sub-cycle for fast response, typically when Active Power Balancing is disabled.
Voltage sag and swell limiting
10 ms time constant; overrides the droop response
Reactive current overshoot
No more than 5% of steady-state output
The current loop is fast enough to respond within a tenth of a cycle. The droop response is deliberately slowed to five seconds so that the unit regulates steady-state voltage rather than chasing transients. Fast events are handled separately: if a phase reaches 180 V or 277 V, the sag and swell function commands maximum reactive power with a 10 ms time constant and overrides the droop.
9. What to specify at commissioning
Four droop set points, plus symmetrical or asymmetrical slopes.
Per-phase control enabled, or average-voltage mode if a network standard requires it.
Active Power Balancing: disabled, gain-based, or optimal X/R.
For gain-based operation: P priority or Q priority, chosen from the local X/R ratio — Q priority for overhead and other reactive feeders, P priority for cable and other resistive feeders.
For optimal X/R operation: the X/R ratio, from the network model or estimated during commissioning.
For settings files, network studies or a copy of the EcoVAR ALTO user manual, contact EcoJoule Energy at sales@ecojoule.com or your regional distributor.
Australian energy grid technology company EcoJoule Energy has secured its first sale into Malaysia, marking another significant milestone in the company’s international expansion and adding one of Southeast Asia’s most important electricity markets to its growing global footprint.
The sale to Tenaga Nasional Berhad (TNB), Malaysia’s national electricity company and operator of the electricity grid throughout Peninsular Malaysia and Kuala Lumpur, includes multiple EcoVAR™ ALTO pole-mounted STATCOMs and EcoSTORE™ pole-mounted Battery Energy Storage System (BESS) units.
The first shipment of EcoVAR units left Australia this week, with the EcoSTORE units to leave in approximately eight weeks.
The agreement further expands EcoJoule Energy’s international presence, which now spans almost ten countries, including Australia, New Zealand, Hong Kong, Belgium, Spain, the United Kingdom, Lithuania, Israel and now Malaysia.
EcoJoule Energy Founder and CEO Dr Mike Wishart said the new sale reflected growing global demand for technologies that help electricity networks manage the growth of renewable energy and the impact on the energy grid.
“Malaysia represents an important new market for EcoJoule and demonstrates the increasing international recognition of Australian innovation in electricity network management,” Dr Wishart said.
“Across the world, network operators are facing many of the same challenges. As solar penetration continues to increase, particularly on distribution networks, utilities need smarter and more flexible ways to manage voltage stability and power quality.”
“We are seeing strong demand for STATCOM technologies because they provide a highly effective solution for maintaining grid stability, while enabling greater levels of renewable energy integration.
“Utilities are looking for practical, cost-effective tools that help them manage the energy transition without relying solely on traditional network augmentation that can cost tens of millions of dollars.”
“The challenges facing electricity networks in Asia, Europe and Australia share a common theme – the transition to cleaner energy is creating increasingly dynamic and complex power flows. EcoJoule’s technologies are designed specifically to help networks adapt to that transition efficiently and sustainably.”
Solving Complex, Pressing Grid Issues
EcoJoule Chief Commercial Officer Martin van der Linde said the Malaysian deployment highlighted the versatility of the company’s technology platforms and its ability to address a broad range of network challenges.
“Our EcoVAR and EcoSTORE platforms have been developed to solve some of the most pressing issues facing modern electricity networks,” Mr van der Linde said.
“What makes the technology unique is its ability to address multiple challenges through a flexible, pole-mounted solution that can be rapidly deployed where it is needed most.”
“Whether utilities are dealing with voltage variability caused by rooftop solar, phase imbalance, peak demand constraints, increasing electrification, or the need for distributed energy storage, our technology provides network operators with greater visibility, control and flexibility.”
“The global energy transition is creating increasingly complex energy flows throughout distribution networks. EcoJoule’s solutions help operators manage that complexity while maximising the use of existing infrastructure and improving reliability for customers.”
EcoVAR™ is a pole-mounted Static Synchronous Compensator (STATCOM) that uses advanced power electronics and software to regulate voltage and reactive power on low-voltage networks in real time. The technology enables network operators to integrate greater levels of distributed renewable energy and electrification technologies while improving power quality and reducing the need for costly network upgrades.
EcoSTORE™ is EcoJoule’s pole-mounted battery energy storage platform, designed to provide distributed storage capacity within local electricity networks. The system helps manage peak demand, supports renewable energy integration, improves network resilience and enables more efficient utilisation of grid infrastructure.
The Malaysian project follows a series of successful deployments of EcoJoule technologies across Australia and international markets, reinforcing the adaptability of the company’s solutions across diverse network conditions and regulatory environments.
Established nearly a decade ago, EcoJoule Energy is a 100 per cent Australian-owned company providing innovative solutions that help electricity distributors integrate renewable energy, improve power quality and manage grid reliability.